Failure Event - South Korea, Haenam - 27 May 2020

From EPRI Storage Wiki
Jump to navigation Jump to search

Overview

Event DetailsSMW-Info-button.png
Location: South Korea, Haenam
Capacity (MW):
Capacity (MWh):
Battery Module:
Integrator:
Application: Solar Integration
Installation: Field
Enclosure Type: Prefab
Event Date: 27 May 2020
System Age (yr): 2.2
Extent of Damage: Fire
State During Accident:
Description: The BESS at a solar + storage facility caught fire. The South Korean government had implemented an upper limit of SOC of 90% for outdoor installations at the beginning of the year, but it was confirmed that the company had continued to operate with an upper limit of SOC of 95% as before. The cause is suspected to be battery deterioration due to overcharging or BMS error.
Source: E2 News (Translated)
Additional Resources: E2 News (Original source, Korean)
Note: Missing values in this table reflect unknowns.

If you have any details or corrections you would like to contribute to the database please reach out to our Storage Safety email.