Failure Event - US, AZ, Surprise - 19 Apr 2019
Jump to navigation
Jump to search
Overview
Event Details | |
---|---|
Location: | US, AZ, Surprise |
Capacity (MW): | 2 |
Capacity (MWh): | 2 |
Battery Module: | LG Chem [NMC] |
Integrator: | AES/Fluence |
Application: | Volt Reg., PQ, Solar int. |
Installation: | Substation |
Enclosure Type: | Prefab |
Event Date: | 19 April 2019 |
System Age (yr): | 2.1 |
Extent of Damage: | Explosion |
State During Accident: | |
Description: | The cause was found to be an internal cell defect, which initiated a cascading thermal runaway event. Alarms and the clean agent fire suppression system activated but was not capable of preventing or stopping cascading thermal runaway in a BESS. Three hours after thermal runaway was intiated, firefighters opened a door to the battery container, agitating accumulated flammable gases and allowing the gases to contact a heat source or spark. Minutes later, an explosion occurred, injuring several firefighters. |
Source: | APS Investigation Report |
Additional Resources: |
- Note: Missing values in this table reflect unknowns.
If you have any details or corrections you would like to contribute to the database please reach out to our Storage Safety email.