The State of Energy Storage: Drivers and Big Picture

From EPRI Storage Wiki
Jump to navigation Jump to search


Under construction icon-blue.png
This page is under development. In the meantime, feel free to browse. Please check back later for additional changes.


Decreases in Technology Costs

Massive research and development investment and manufacturing scale-up has driven costs down for lithium ion battery storage. This was initially driven by the consumer electronics market (e.g. cell phones and laptops) and more recently accelerated by the electric vehicle market. There has been an almost 90% reduction in $/kWh cost in the last decade and lithium ion costs are expected to continue to decrease with additional manufacturing improvements and economies of scale.

Bloomberg New Energy Finance projects 2030 lithium ion pack costs at $62/kWh based on observed prices and an 18% learning rate. Source: BNEF

Increasing Renewable Generation

Solar PV is driving over generation in midday and increased evening ramp drives value for flexibility and energy storage. Wind energy is similarly driving flexibility needs.

Evolving Utility Needs

  • The grid is sized for infrequent peak needs and using energy storage for peak load reduction provides significant cost reduction opportunity to electricity customers.
  • Utility asset infrastructure is aging and peak load reduction may extend asset life and offer opportunity to consider investment in new technologies.
  • Storage is being considered in generation planning. Battery storage costs may cross-over combustion turbines in the next decade. Accounting for operational benefits, breakeven may be sooner.

Increasing Utility Customer Choice and Engagement

Customers (residential, commercial, industrial) are considering energy storage for

  • Bill savings
  • Increased energy independence
  • Renewable energy goals
  • Backup premise or critical loads

Policy and Regulatory Changes

Federal Policy
FERC Order 755 Frequency Regulation Compensation in Organized Markets

  • Pay for Performance compensation based on speed and accuracy


FERC Order 841 Electric Storage Participation in Markets Operated by RTOs and ISOs

  • Storage can participate in energy, ancillary services, and capacity markets when technically able
  • Clarifies technical provisions for energy storage


FERC Order 845-A Reform of Generator Interconnection Procedures and Agreements

  • Revises large generator interconnection requirements
  • Allows interconnection below combined nameplate for hybrid systems


FERC Order 2222 Participation of Distributed Energy Resource Aggregations in Markets Operated by RTOs and ISOs

  • Enables Aggregated DER (or Virtual Power Plant) participation in ISO/RTO markets


U.S. State Policy
States are taking varying approaches for energy storage deployment
Es101driver10.png
Procurement Targets: Regulators or legislators set procurement goals and mandates requiring utilities to directly procure or contract storage.
Incentives: Legislators create economic incentives (e.g. rebates or subsidies) for deploying storage; No mandatory procurement 
Resource Plans: State agencies or regulators fund studies or direct utilities to create an energy plan with consideration of storage; No targets or incentives