Below is a table of some of the most popular storage technologies with some extra details.  
Below is a table of some of the most popular storage technologies, click on each for more detail.  


{{#ask:
[[Category:Energy Storage Technology]]
|mainlabel=Storage Technology
|?Has How it Works Description=How It Works
|?Has Efficiency Range=AC Efficiency Range
|?Has Cycle Life=Life
|?Has Maturity Level=Maturity Level / TRL
|?Has Benefits=Benefits
|?Has Challenges=Challenges
|?Has Application=Applications
|?Has Installed Capacity=Installed Capacity
|format=broadtable
|headers=show
}}
<!--
{{#ask:
{{#ask:
  [[Category:Energy Storage Technology]]
  [[Category:Energy Storage Technology]]
Line 127: Line 143:
}}
}}


<!-- 
  |?Has How it Works Description=How it Works
  |?Has How it Works Description=How it Works
  |?Has Varieties=Variations
  |?Has Varieties=Variations

Revision as of 16:39, 22 December 2021


Under construction icon-blue.png
This page is under development. In the meantime, feel free to browse. Please check back later for additional changes.

Defining Energy Storage

People often think of grid energy storage as electricity in / electricity out with some energy loss in between due to inefficiencies. A more inclusive "energy storage" definition should include technological nuances like supplemental energy sources (e.g. input fuels or heat injection). One must also consider that energy storage systems can output non-electrical energy in the form of heat, cooling, or fuel sources (e.g. hydrogen).

A generalized energy storage visual

Technical Characteristics of Energy Storage

The specifics of a project's use case(s) will dictate the optimal system attributes. Understanding these attributes, and the trade-offs between them, will help with the selection of a specific technology. For an exhaustive list of considerations, refer to the ESIC Technical Specification Template.

Power, Energy, and Duration

Some of the most fundamental energy storage attributes are power (measured in Watts) and energy (measured in Watt-Hours). Energy storage power is usually provided in kilowatts (kW), megawatts (MW), or gigawatts (GW), while energy is the integral of power over time, so measured in kilowatt-hours (kWh), megawatts-hours (MWh), or gigawatts-hours (GWh), depending on the scale of the system. Sometimes, a duration (hours) is specified instead of energy, this is calculated by dividing the energy (watt-hours) by the power (watts) to return hours. This provides an estimate for the amount of time a system could operate at it's rated power, though in reality, the true time a system takes to charge or discharge is dependent on many factors or limitations.

In this analogy, power (watts) is analogous to the keg’s flow rate (pints/hour) Energy (watt-hours) is analogous to the keg size (pints) Knowing the power (keg flow rate) and energy (amount of beer) we know how long we will have electricity (beer) for.

Relationship Between Technologies and Their Ideal Applications

Different technologies have their own ideal energy-to-power ratio (i.e. duration) which makes them suitable for specific classes of use cases. The figure below breaks the duration domain (x-axis) into 4 different use case bins with common technologies added to the areas that they tend to perform best. Some energy storage technologies, like super-capacitors, are best at responding quickly and come in small modular form factors making them ideal for fast, "power" services like frequency response. Other technologies like pumped hydro are only feasible on a large scale, so are best suited for high "energy" services like energy time shifting.

Technology Modular Application.png

Key Storage Technology Attributes for Project Evaluation

There are many technology attributes that are most important when performing site-specific project evaluations. So, what technology you ultimately decide to deploy will be a function of what is required for a specific use case. These attributes include: safety, expected operational life, deployment timeline, performance, technology maturity, siting considerations, lifecycle costs, and environmental or public health considerations.

Storage Tech Attributes.png


Performance Attributes

This section will describe a few of the many energy storage performance attributes that should be considered. For a more exhaistive resource please visit the ESIC Energy Storage Test Manual, it is free to the public.


Efficiency: Ratio of the delivered discharge energy to the delivered charge energy, including facility parasitic loads. Many factors impact a system's measured efficiency:

  • The specifics of the efficiency measurement and calculation
  • Location of measurement (e.g. at the DC output of the battery or AC output of the inverters)
  • Auxiliary or parasitic load losses
  • Power level of a given cycle
  • The weather / season
A breakdown of some of the energy inefficiencies that may affect a technology's overall efficiency


Response Time and Ramp Rate: Some energy storage technologies are able to respond quickly to dynamic control sugnals while others require more time to ramp up and respond with accurate output. Fast acting energy storage systems may perform dynamic grid services (like frequency regulation) better than conventional alternatives.

Due to their inherently low inertia, some inverter based energy storage technologies are able to react quickly to control commands.


Operational Life

The operational life of an energy storage system is a tricky concept to define generally, but it typically refers to how long a system is able to operate before degradation prevents the system from safely and reliably performing its objectives. Different technologies will have drastically different degradation time frames and mechanisms, but most degradation impacts can be described by cycle life or calendar life


Cycle Life: Number of times the energy storage system can be charged and discharged before degrading beyond application requirement. Often, factors like each cycle's depth-of-discharge, temperature, and power level affect each cycle's contribution to lifetime degradation.

Cycle life is highly dependent on how the system is operated.


Calendar Life: Number of years the system operates before degrading beyond application requirement. Independent of cycle life.

Systems degradation is also dependent on factors like average resting state-of-charge and average ambient temperature.


Safety

Storing large amounts of energy in a confined space leads to a number of safety risks including fire, chemical, electrical, or physical hazards. Different technologies will have their own inherent safety risks or benefits depending on the mechanisms used to store energy. The safety of a system depends heavily upon proper planning and integration early on in a storage project. For help assessing fire risks, please refer to the ESIC Fire Hazard Mitigation Analysis, it is free to the public.


Survey of Technologies

Storage technologies can be grouped into a few categories based on the mechanism that is used to convert and store energy. The categories, with some popular examples, include:

Electrochemical (i.e. Batteries)

  • Lithuim ion
  • Lead acid
  • Sodium-beta
  • Flow batteries

Electromechanical

  • Pumped hydro
  • Compressed air (CAES)
  • Flywheel

Chemical

  • Hydrogen
  • Synthetic fuels

Electrical

  • Capacitors
  • Superconducting magnetic energy storage (SMES)

Thermal

  • Molten salt storage
  • Thermal storage

Below is a table of some of the most popular storage technologies, click on each for more detail.

Storage TechnologyHow It WorksAC Efficiency RangeLifeMaturity Level / TRLBenefitsChallengesApplicationsInstalled Capacity
Compressed Air Energy Storage (CAES)Air is compressed (charging), stored, and expanded (discharging).40-55%30 years
  • Mature bulk storage
  • Low cost per kWh potential
  • Geographical limitations
  • Requires fuel for heating producing CO2 emissions
Bulk, long-duration services~500 MW
Flow BatteriesLiquid anode (anolyte) and cathode (catholyte). Electrolytes flow through reaction cell and charge transfer occurs at a membrane. Vanadium-based chemistry is most mature, other chemistries being developed.50-75%20 years, >100,000 cycles (claimed)
  • Power (reactor size) decoupled from Energy (tank size)
  • Limited impact of cycling on degradation
  • Higher fire safety than lithium ion
  • Lower energy density
  • Potential environmental spill risk
  • OK to poor efficiency observed to-date
  • Added system complexity with pumps etc.
Energy shifting for renewable integration, T&D deferral, potential for longer duration~100 MW
Flywheel Energy StorageRotating mass stores rotational kinetic energy.85-90%>100,000 cycles
  • Fast response time
  • High power capability
  • Low energy capacity
  • High self discharge rates
Power quality, frequency regulation, wind generation stabilization; high energy flywheels are being developed for longer duration applications.~60 MW
Lithium Ion BatteriesShuttle lithium ions (Li+) between cathode (+) and anode (-). Fully charged when Lithium ions are fully intercalated in the anode.80-92%3,000 - 10,000 cycles 10 - 20 years
  • High power and energy density
  • Low self-discharge rate
  • High roundtrip efficiency
  • Flexible configurations
  • Leverage cost reductions from consumer electronics and electric vehicle markets
  • Cycle life limitations, especially with high depth of discharge
  • Safety concerns around fire and explosion risk
  • Supply chain constraints
Diverse applications from minutes to hours duration and from small scale residential to transmission connected.>10 GW
Pumped Hydroelectric Energy StorageGravitational potential energy ↔ kinetic energy ↔ electricity Water is pumped up hill with excess electrical energy which is stored as gravitational potential energy. When energy is needed, water flows down through the generator to produce electricity.70-85%60-100 years1
  • Ability to integrate inverter-based renewables
  • Mature, flexible, bulk storage
  • Capital intensive
  • Geographical limits
  • Permitting (open-loop)
Bulk, long-duration services, power regulation and load following>160 GW
Thermal Energy Storage - End UseStoring energy by heating or cooling a storage medium for end use in a thermal application.Not applicable10 - 15 years
  • Thermal demands are a large part of building and commercial loads
  • System engineering challenges to enable low cost installations
  • Ice, Chilled Water, Water Heater
  • Used for building and district heating and cooling, cold food storage
Cooling: ~14 GWh2
Thermal Energy Storage - GenerationStoring energy by heating or cooling a storage medium and converting to electricity.35-60%20 - 30 years
  • Low cost incremental energy
  • Non-toxic materials
  • Can be integrated with existing power gen units
  • Low round trip efficiency 
  • System engineering challenges to enable low cost installations
  • Molten Salt, Liquid Air, Concrete/Gravel/Sand Thermal, Electro-Thermal Energy Storage
  • Used for bulk energy storage applications
~4 GW (mostly molten salt)


Research and Resources at EPRI

Current Research Focus

  • Long duration storage
  • Non-lithium storage
  • Lithium ion advancements

Resources and Engagement Opportunities

Resource Access Level
Webcast Recording on Energy Storage Technology Publicly Available
Emerging Energy Storage Technology Testing and Demonstration Supplemental Project Supplemental Funders
Energy Storage Technology Database Program 94: Energy Storage and Distributed Generation or

Program 66: Advanced Generation and Bulk Energy Storage

Strategic Intelligence (SI) Articles Program 94: Energy Storage and Distributed Generation
DER Forum: Technologies Discussion Program 94: Energy Storage and Distributed Generation