Failure Event - US, AZ, Surprise - 19 Apr 2019

From EPRI Storage Wiki
Revision as of 12:40, 14 April 2022 by Jthompson (talk | contribs)
Jump to navigation Jump to search

Overview

Event DetailsSMW-Info-button.png
Location: US, AZ, Surprise
Capacity (MW): 2
Capacity (MWh): 2
Battery Module: LG Chem [NMC]
Integrator: AES/Fluence
Application: Volt Reg., PQ, Solar int.
Installation: Substation
Enclosure Type: Prefab
Event Date: 19 April 2019
System Age (yr): 2.1
Extent of Damage: Explosion
State During Accident:
Description: The cause was found to be an internal cell defect, which initiated a cascading thermal runaway event. Alarms and the clean agent fire suppression system activated but was not capable of preventing or stopping cascading thermal runaway in a BESS. Three hours after thermal runaway was intiated, firefighters opened a door to the battery container, agitating accumulated flammable gases and allowing the gases to contact a heat source or spark. Minutes later, an explosion occurred, injuring several firefighters.
Source: APS Investigation Report
Additional Resources:
Note: Missing values in this table reflect unknowns.

If you have any details or corrections you would like to contribute to the database please reach out to Dirk Long.