=Introduction to Grid Services=
=Introduction to Grid Services=
The economics of energy storage is reliant on the services and markets that exist on the electrical grid which energy storage can participate in. These value streams differ by region, electrical system, and grid domain (i.e. transmission, distribution, customer-sited).  
The economics of energy storage is reliant on the services and markets that exist on the electrical grid which energy storage can participate in. These value streams differ by region, electrical system, and grid domain (i.e. transmission, distribution, customer-sited).  
[[File:ES applications Across the Grid.png|none|thumb|800px|Storage can be deployed at any level throughout the power grid, from the generation and transmission level down to the customer level.]]
[[File:ES applications Across the Grid.png|none|thumb|650px|Storage can be deployed at any level throughout the power grid, from the generation and transmission level down to the customer level.]]


Regardless of the situation, at a high level, energy storage can be utilized across the grid in the following ways:
Regardless of the situation, at a high level, energy storage can be utilized across the grid in the following ways:
Line 17: Line 15:
The figure below provides a list of the services that energy storage can provide at the transmission or bulk energy storage level (generally 10MW or more). These include generation capacity (sometimes called resource adequacy), flexible capacity (sometimes called flexible resource adequacy), virtual transmission capacity (support transmission reliability or alleviate congestion), energy time shift, ancillary services, black start, and frequency response. This section provides more detail.
The figure below provides a list of the services that energy storage can provide at the transmission or bulk energy storage level (generally 10MW or more). These include generation capacity (sometimes called resource adequacy), flexible capacity (sometimes called flexible resource adequacy), virtual transmission capacity (support transmission reliability or alleviate congestion), energy time shift, ancillary services, black start, and frequency response. This section provides more detail.


[[File:Transmission Sited Storage Applications.png|none|thumb|800px|In some scenarios, bulk storage may serve as an alternative to generators or transmission assets.]]
[[File:Transmission Sited Storage Applications.png|none|thumb|650px]]


===Generation Capacity (Resource Adequacy)===
===Generation Capacity (Resource Adequacy)===
Generation capacity is the capability and availability of a resource to contribute to system load needs. Capacity resources are typically committed months to years in advance. As demand and resource mixes change, including generator retirements, new resources are needed to ensure capacity needs are met during all hours and conditions. Assuming sufficient storage duration and reliable response times, energy storage may provide reliable load peak reduction. However, energy storage is more challenging to model and assess than traditional generation, because of its limited energy capacity.
Generation capacity is the capability and availability of a resource to contribute to system load needs. Capacity resources are typically committed months to years in advance. As demand and resource mixes change, including generator retirements, new resources are needed to ensure capacity needs are met during all hours and conditions. Assuming sufficient storage duration and reliable response times, energy storage may provide reliable load peak reduction. However, energy storage is more challenging to model and assess than traditional generation, because of its limited energy capacity.


[[File:Energy storage scenarios CAISO demand.png|none|thumb|800px|This figure shows one day of CAISO demand data with three different energy storage duration scenarios to show how storage as a capacity resource can produce more favorable system demand profiles.]]
[[File:Energy storage scenarios CAISO demand.png|none|thumb|650px|This figure shows one day of CAISO demand data with three different energy storage duration scenarios to show how storage as a capacity resource can produce more favorable system demand profiles.]]


===Flexible capacity===
===Flexible capacity===
As more renewables are deployed, daily fluctuations (i.e. ramp rate requirements) in traditional energy generation are increasing. Grid planners must consider these ramp rates in long-term generation resource planning. Energy storage can alleviate ramp rate requirements by absorbing or releasing energy to effectively reduce the maximum ramp rate required by generators.
As more renewables are deployed, daily fluctuations (i.e. ramp rate requirements) in traditional energy generation are increasing. Grid planners must consider these ramp rates in long-term generation resource planning. Energy storage can alleviate ramp rate requirements by absorbing or releasing energy to effectively reduce the maximum ramp rate required by generators.


[[File:Flexible Capacity Transmission.png|none|thumb|800px|Because energy storage can generally charge or discharge at its rated power, it provides more flexibility than a traditional generation asset which can only produce energy in a limited range.]]
[[File:Flexible Capacity Transmission.png|none|thumb|650px|Because energy storage can generally charge or discharge at its rated power, it provides more flexibility than a traditional generation asset which can only produce energy in a limited range.]]


===Virtual transmission capacity (reliability/congestion)===
===Virtual transmission capacity (reliability/congestion)===
Circuit load growth downstream of transmission assets drives the need for transmission upgrade investments to ensure reliability in both normal and contingency situations. If appropriately sized and placed on the transmission system, energy storage can reliably reduce peak load below capacity threshold by charging during low load times and discharging to serve loads when the threat of transmission system overload arises. With this strategy, utilities may delay traditional transmission upgrade investments for several years resulting in time-value of money savings and rate-payer benefits.
Circuit load growth downstream of transmission assets drives the need for transmission upgrade investments to ensure reliability in both normal and contingency situations. If appropriately sized and placed on the transmission system, energy storage can reliably reduce peak load below capacity threshold by charging during low load times and discharging to serve loads when the threat of transmission system overload arises. With this strategy, utilities may delay traditional transmission upgrade investments for several years resulting in time-value of money savings and rate-payer benefits.


[[File:Transmission Asset Deferral.png|none|thumb|800px|If a transmission system will become overloaded, operators can upgrade that transmission infrastructure to accommodate the new peak demand. Instead, they may decide to install energy storage downstream of the overloaded asset to strategically discharge energy during the brief times where the demand is peaking.]]
[[File:Transmission Asset Deferral.png|none|thumb|650px|If a transmission system will become overloaded, operators can upgrade that transmission infrastructure to accommodate the new peak demand. Instead, they may decide to install energy storage downstream of the overloaded asset to strategically discharge energy during the brief times where the demand is peaking.]]


===Energy time-shifting===
===Energy time-shifting===
Energy time-shift recognizes an opportunity to economically move energy demand through time taking advantage of fluctuations in the marginal cost of electricity production. To do this, storage can charge when the price of electricity is low (or even negative) and discharge when prices are high. The value of energy time-shift depends heavily on market structure, load growth, and generation mix.
[[File:Energy Time Shift Example.png|none|thumb|650px|An example of energy time-shifting where a battery charges during low-price times and discharges during times of high energy cost.]]
===Ancillary services===
===Ancillary services===
===Black start capability===
Ancillary Services are reserve services necessary to support the transmission of electric power from seller to purchaser, given reliability obligations within control areas. The electricity grid operates as a just-in-time delivery system and system operators are responsible for managing voltage, frequency, and system restoration. Variable generation sources such as wind and solar tend to increase uncertainty and variability on the grid. Energy storage, as a flexible resource, can provide instantaneous reserves to balance the grid and leverage it's fast-acting power electronics to perform services like Volt/VAR regulation.
===Frequency response===
 
Common ancillary services include:
* Frequency Regulation
* Spinning Reserve
* Non-Spinning Reserve
* Frequency Response
* Black Start
* Voltage/VAR Regulation


==Distribution-Connected Energy Storage==
==Distribution-Connected Energy Storage==
The figure below provides a list of the services that energy storage can provide at the distribution level (generally in the 10kW-10MW range). These include virtual distribution capacity, power quality support, resilience / backup power for microgrids, as well as the possibility to provide transmission support in certain scenarios.
[[File:Distribution Connected Services.png|none|thumb|650px|Depending on the scenario, it may be possible for a distribution connected energy storage system to provide benefits to the transmission system. For example, a distribution-connected storage system could provide energy to loads during times of high transmission stress thereby preventing transmission overloading.]]
===Virtual distribution capacity===
This service is similar to the "Virtual transmission capacity", just at the distribution level. In the example depicted below, some time in the near future, more load (homes) will exist on the distribution feeder than the feeder's transformer can handle during peak times. Distribution planners can either upgrade that transformer now, or install an energy storage system downstream of the transformer to ensure its limit is not exceeded for a few more years. In some cases, this energy storage purchase and traditional asset upgrade deferral can provide favorable economics. It is also possible for distribution-connected energy storage systems to provide similar virtual services to the upstream transmission network.
[[File:Virtual Distribution Capacity .png|none|thumb|650px|Energy storage can defer or avoid traditional utility upgrades resulting in time value of money cost savings.]]


==Customer-Sited Energy Storage==
==Customer-Sited Energy Storage==
The figure below provides a list of the services that energy storage can provide at the customer-sited level (generally in the 2kW-2MW range). These include customer bill savings, power quality enhancements, resilience / backup power for microgrids, as well as the possibility to provide transmission and/or distribution support in certain scenarios.
[[File:Customer Energy Storage.png|none|thumb|650px|It may be possible to stack distribution and transmission-level services to some degree.]]
==Value Stacking==
Each grid service performed by a battery may provide some economic value, or benefit, but one service alone may not provide enough value to overcome the lifetime costs of the installation. If a specific scenario allows it, it may be possible to approach multiple grid services with one project to improve a projects economics. Keep in mind, there may be regulatory or technical complications that prevent the a project from attempting multiple stacked services.
[[File:Transmission Value Stacking.png|none|thumb|650px|One grid service alone may not provide enough value to justify the lifetime costs of an energy storage system. In the right environment, multiple grid services can be stacked to increase the lifetime value.]]
===Understanding Service Compatibility===
When value stacking, energy storage service compatibility only flows from bottom up; customer storage may provide distribution and transmission-level services, but transmission storage can NOT provide distribution or customer services.
'''Reliability vs. Economic Services'''
Reliability services take priority over economic services. For example transmission / distribution deferral services are higher priority than market services.
'''Local vs. System Level'''
In general, local objectives supersede system objectives when there is a conflict. For example, transmission / distribution deferral is a higher priority than resource adequacy, though operations should be designed such that reliability services never conflict.


=Cost Components and Trends=
=Cost Components and Trends=
Clarity on costs is a critical step in energy storage economics. Economic analysis of energy storage systems need to clearly articulate what major components are included in the scope of cost. The schematic below shows the major components of an energy storage system. System components consist of batteries, power conversion system, transformer, switchgear, and monitoring and control. A proper economic analysis identifies the cost associated with each of these components or provides reasoning for exclusion.
An economic analysis of energy storage systems should clearly articulate what major components are included in the scope of cost. The schematic below shows the major components of an energy storage system. System components consist of batteries, power conversion system, transformer, switchgear, and monitoring and control. A proper economic analysis identifies the costs associated with each of these components.
[[File:Es101cost10.png|none|thumb|550px|Source: EPRI. Understanding the components of energy storage systems is a critical first step to understanding energy storage economics.]]  
 
In addition to identification of major components, there are key BESS services that occur throughout the system's lifetime that need to be accounted for in an economic analysis. The left side of the graphic below shows the beginning of life stacked costs for battery energy storage systems. As shown in the upfront owners' costs, the largest upfront cost is the battery itself. One important consideration given the significant battery cost are the sizing assumptions that are used for cost estimates. Of the procured energy, a fraction of that energy is delivered to the customer and some fraction is reserved for safety and performance margins, degradation overbuild, AC/DC losses, or is electrochemically inaccessible. Additionally, the graphic shows costs of services throughout BESS operation. These services include operating expenses, fixed system maintenance, and decommissioning and end of life services.
[[File:Es101cost10.png|none|thumb|650px|Source: EPRI. Understanding the components of energy storage systems is a critical first step to understanding energy storage economics.]]  
[[File:Scope_of_Supply.png|none|thumb|550px|Source: EPRI. "Battery Energy Storage Lifecycle Cost Assessment Summary 2020"- A clear scope of supply is needed to determine owner costs. This includes services and equipment.<ref>EPRI: "[https://www.epri.com/research/products/000000003002020048 Battery Energy Storage Lifecycle Cost Assessment Summary 2020]"</ref>]]
 
In addition to identification of major components, there are key BESS services that occur throughout the system's lifetime that need to be accounted for in an economic analysis. The left side of the graphic below shows the beginning of life stacked costs for battery energy storage systems. As shown in the owner's upfront costs, the largest upfront cost is the battery itself. One important consideration, given the significant battery costs, is the sizing assumptions that are used for cost estimates. Often, only a fraction of the procured energy is actually delivered to the customer and some fraction is reserved for safety and performance margins, degradation overbuild, AC/DC losses, or is electrochemically inaccessible. Additionally, the graphic shows relative costs for services throughout BESS operation. These services include operating expenses, fixed system maintenance, and decommissioning and end of life services.
 
[[File:Lifetime Cost Estimates.png|none|thumb|650px|A clear scope of supply is needed to determine owner costs. This includes services and equipment.<ref>EPRI: "[https://www.epri.com/research/products/000000003002020048 Battery Energy Storage Lifecycle Cost Assessment Summary 2020]"</ref>]]


Other generation resource costs are often communicated on a $/kW basis, but energy storage has both power and energy components and the normalized cost will vary with duration. This is highlighted in two examples below where it's clear that the longer duration system has a higher cost per kW of power.  
Other generation resource costs are often communicated on a $/kW basis, but energy storage has both power and energy components and the normalized cost will vary with duration. This is highlighted in two examples below where it's clear that the longer duration system has a higher cost per kW of power.  
<div><ul>  
<div><ul>  
<li style="display: inline-block;"> [[File:Es101cost20.png|thumb|none|500px|Source: EPRI. 4 Hour Duration System.]] </li>
<li style="display: inline-block;"> [[File:Es101cost20.png|thumb|none|650px|Source: EPRI. 4 Hour Duration System.]] </li>
<li style="display: inline-block;"> [[File:Es101cost30.png|thumb|none|500px|Source: EPRI. 2 Hour Duration System.]] </li>
<li style="display: inline-block;"> [[File:Es101cost30.png|thumb|none|650px|Source: EPRI. 2 Hour Duration System.]] </li>
</ul></div>
</ul></div>


The image below shows lithium ion cost projections from a [https://www.epri.com/research/products/000000003002020048 2020 EPRI cost study]. As demonstrated in the two examples above, the longer duration systems, as of 2020, are more expensive per kW than the shorter duration systems. However, EPRI's cost study projects that the cost per kW of 8 hour duration lithium ion systems is decreasing at a faster rate than 2 hour lithium ion systems.
The image below shows lithium ion cost projections from a [https://www.epri.com/research/products/000000003002020048 2020 EPRI cost study]. As demonstrated in the two examples above, the longer duration systems, as of 2020, are more expensive per kW than the shorter duration systems. However, EPRI's cost study projects that the cost per kW of 8 hour duration lithium ion systems is decreasing at a faster rate than 2 hour lithium ion systems.


[[File:Li_Ion_Cost_Projection_2020.png|none|thumb|550px|Source: EPRI. "Lithium Ion Installed Cost Projections": [https://www.epri.com/research/products/000000003002020048 Battery Energy Storage Lifecycle Cost Assessment Summary 2020]]]
[[File:Li_Ion_Cost_Projection_2020.png|none|thumb|650px|Lithium Ion Installed Cost Projections<ref>EPRI: "[https://www.epri.com/research/products/000000003002020048 Battery Energy Storage Lifecycle Cost Assessment Summary 2020]"</ref>]]
 


=Modeling Energy Storage=
=Modeling Energy Storage=
'''Challenges to modeling energy storage include:'''
Advanced energy storage is a difficult technology to model owing to its limited energy capacity. Operating an energy storage system now can limit its ability to operate in the future. Additionally, energy storage is not yet a common grid asset and is subject to rapidly changing rules, regulations, and standards. But, the flexibility of energy storage can provide a lot of value when operated well and with consideration for the degradation of the system owing to their ability to go from charging to discharging and vice versa quickly and without interruption. Typically, energy storage systems do not serve just one application and instead leverage their flexibility across several stacked services. Service stacking presents additional modeling challenges, though, because the requirements imposed by each service need to be meet in parallel. The need to ensure a storage system can provide stacked services without running out of stored energy typically necessitates detailed, site-specific time series modeling.
*Storage is not yet a common grid asset
*Rules and regulations are still evolving
*Benefit stacking is appealing, but is it possible?
**More services = more value
**More services = more requirements
**Can these requirements be satisfied?
*Storage value analyses are site-specific
*Complex co-optimization between storage technologies, objectives, and constraints


<br> '''Understanding Service Compatibility'''
=Other Resources=
*Energy Storage Services Hierarchy
==EPRI Tools to Support Valuation Modeling==
**Energy storage services only flow from bottom up, customer storage may provide distribution and transmission-level services, but transmission storage can NOT provide distribution or customer services
* [http://storagevet.com/ StorageVET]
*Reliability vs. Economic
* [http://der-vet.com/ DER-VET]
**Reliability takes priority (e.g. T&D deferral higher priority than market services)
**Long-term planning constraints take priority to economic optimization and constraints roll-up; Multi-year >> Annual >> Monthly >> Day-ahead >> Real-time
*Local vs. System Level
**Local objectives generally supersede system objectives when there is a conflict (e.g. T&D deferral higher priority than resource adequacy) although should be designed so that reliability services never conflict


=Resources=
==Reports==
<br>'''EPRI Tools to Support Valuation Modeling'''
<br>[http://storagevet.com/ StorageVET]
<br>[http://der-vet.com/ DER-VET]
<br>'''Reports'''
{| class="wikitable"
{| class="wikitable"
! style="text-align:left;"| Resource
! style="text-align:left;"| Resource
! Access Level
! Access Level
|-
|-
|[https://membercenter.epri.com/Programs/053125/pages/productabstract.aspx?ProductId=000000003002016637 EPRI Solar Plus Storage Cost Assessment and Design Considerations: Executive Summary (2019)]
|[https://www.epri.com/research/products/000000003002016637 EPRI Solar Plus Storage Cost Assessment and Design Considerations: Executive Summary (2019)]
|Publicly Available
|Publicly Available
|-
|-
|[https://membercenter.epri.com/Programs/053125/pages/productabstract.aspx?ProductId=000000003002013958 EPRI Energy Storage Technology and Cost Assessment: Executive Summary (2018)]
|[https://www.epri.com/research/products/000000003002013958 EPRI Energy Storage Technology and Cost Assessment: Executive Summary (2018)]
|Publicly Available
|Publicly Available
|-
|-
|[https://membercenter.epri.com/Programs/053125/pages/productabstract.aspx?ProductId=000000003002013529 ESIC Energy Storage Cost Tool and Template]
|[https://www.epri.com/research/products/000000003002013529 ESIC Energy Storage Cost Tool and Template]
|Publicly Available
|Publicly Available
|-
|-
|[https://membercenter.epri.com/Programs/053125/pages/productabstract.aspx?ProductId=000000003002008901 Energy Storage Valuation in California: Policy Planning and Market Information Relevant to the StorageVET Model]
|[https://www.epri.com/research/products/000000003002008901 Energy Storage Valuation in California: Policy Planning and Market Information Relevant to the StorageVET Model]
|Publicly Available
|Publicly Available
|}
|}

Latest revision as of 13:39, 21 December 2021


Introduction to Grid Services

The economics of energy storage is reliant on the services and markets that exist on the electrical grid which energy storage can participate in. These value streams differ by region, electrical system, and grid domain (i.e. transmission, distribution, customer-sited).

Storage can be deployed at any level throughout the power grid, from the generation and transmission level down to the customer level.

Regardless of the situation, at a high level, energy storage can be utilized across the grid in the following ways:

  • Capacity Resource: On the electric grid, capacity is synonymous with power, and to be a capacity resource is to provide power that is reliable and firm, so that it can be dispatched when needed. For example, energy storage can charge itself during times when there's excess capacity and essentially become a capacity resource for times when load is peaking in a particular location or region.
  • Flexibility Resource: Energy storage has the ability to increase (charge), or decrease (discharge), the total load on the grid at different times very quickly. This characteristic can be leveraged to decrease ramp rate requirements and stresses on traditional assets during times when high generation ramp rates are required. For example, in the early afternoon when grid load demand is low and renewable generation is peaking, traditional generators must quickly ramp down to prevent over-generation on the system. During this time, energy storage can charge itself with excess renewable energy and discharge the energy later in the afternoon, as renewables ramp down and load demand increases.
  • Backup Resource: Energy storage can act as a reservoir for energy which can be saved and used when it is needed. If electric power service is disrupted and energy storage is connected to a critical load, the load can use the energy reserve to ride out the disruption.
  • Power Quality Resource: Energy storage can be used to affect the voltage or the VARs at a particular point on the grid. This can be accomplished by energy storage systems that have inverters that are capable of "4 quadrant" operation. This functionality enables the inverter and storage system to either produce or absorb VARs which can affect the voltage voltage around the point of interconnection.


Transmission-Connected and Bulk Energy Storage

The figure below provides a list of the services that energy storage can provide at the transmission or bulk energy storage level (generally 10MW or more). These include generation capacity (sometimes called resource adequacy), flexible capacity (sometimes called flexible resource adequacy), virtual transmission capacity (support transmission reliability or alleviate congestion), energy time shift, ancillary services, black start, and frequency response. This section provides more detail.

Transmission Sited Storage Applications.png

Generation Capacity (Resource Adequacy)

Generation capacity is the capability and availability of a resource to contribute to system load needs. Capacity resources are typically committed months to years in advance. As demand and resource mixes change, including generator retirements, new resources are needed to ensure capacity needs are met during all hours and conditions. Assuming sufficient storage duration and reliable response times, energy storage may provide reliable load peak reduction. However, energy storage is more challenging to model and assess than traditional generation, because of its limited energy capacity.

This figure shows one day of CAISO demand data with three different energy storage duration scenarios to show how storage as a capacity resource can produce more favorable system demand profiles.

Flexible capacity

As more renewables are deployed, daily fluctuations (i.e. ramp rate requirements) in traditional energy generation are increasing. Grid planners must consider these ramp rates in long-term generation resource planning. Energy storage can alleviate ramp rate requirements by absorbing or releasing energy to effectively reduce the maximum ramp rate required by generators.

Because energy storage can generally charge or discharge at its rated power, it provides more flexibility than a traditional generation asset which can only produce energy in a limited range.

Virtual transmission capacity (reliability/congestion)

Circuit load growth downstream of transmission assets drives the need for transmission upgrade investments to ensure reliability in both normal and contingency situations. If appropriately sized and placed on the transmission system, energy storage can reliably reduce peak load below capacity threshold by charging during low load times and discharging to serve loads when the threat of transmission system overload arises. With this strategy, utilities may delay traditional transmission upgrade investments for several years resulting in time-value of money savings and rate-payer benefits.

If a transmission system will become overloaded, operators can upgrade that transmission infrastructure to accommodate the new peak demand. Instead, they may decide to install energy storage downstream of the overloaded asset to strategically discharge energy during the brief times where the demand is peaking.

Energy time-shifting

Energy time-shift recognizes an opportunity to economically move energy demand through time taking advantage of fluctuations in the marginal cost of electricity production. To do this, storage can charge when the price of electricity is low (or even negative) and discharge when prices are high. The value of energy time-shift depends heavily on market structure, load growth, and generation mix.

An example of energy time-shifting where a battery charges during low-price times and discharges during times of high energy cost.

Ancillary services

Ancillary Services are reserve services necessary to support the transmission of electric power from seller to purchaser, given reliability obligations within control areas. The electricity grid operates as a just-in-time delivery system and system operators are responsible for managing voltage, frequency, and system restoration. Variable generation sources such as wind and solar tend to increase uncertainty and variability on the grid. Energy storage, as a flexible resource, can provide instantaneous reserves to balance the grid and leverage it's fast-acting power electronics to perform services like Volt/VAR regulation.

Common ancillary services include:

  • Frequency Regulation
  • Spinning Reserve
  • Non-Spinning Reserve
  • Frequency Response
  • Black Start
  • Voltage/VAR Regulation

Distribution-Connected Energy Storage

The figure below provides a list of the services that energy storage can provide at the distribution level (generally in the 10kW-10MW range). These include virtual distribution capacity, power quality support, resilience / backup power for microgrids, as well as the possibility to provide transmission support in certain scenarios.

Depending on the scenario, it may be possible for a distribution connected energy storage system to provide benefits to the transmission system. For example, a distribution-connected storage system could provide energy to loads during times of high transmission stress thereby preventing transmission overloading.

Virtual distribution capacity

This service is similar to the "Virtual transmission capacity", just at the distribution level. In the example depicted below, some time in the near future, more load (homes) will exist on the distribution feeder than the feeder's transformer can handle during peak times. Distribution planners can either upgrade that transformer now, or install an energy storage system downstream of the transformer to ensure its limit is not exceeded for a few more years. In some cases, this energy storage purchase and traditional asset upgrade deferral can provide favorable economics. It is also possible for distribution-connected energy storage systems to provide similar virtual services to the upstream transmission network.

Energy storage can defer or avoid traditional utility upgrades resulting in time value of money cost savings.

Customer-Sited Energy Storage

The figure below provides a list of the services that energy storage can provide at the customer-sited level (generally in the 2kW-2MW range). These include customer bill savings, power quality enhancements, resilience / backup power for microgrids, as well as the possibility to provide transmission and/or distribution support in certain scenarios.

It may be possible to stack distribution and transmission-level services to some degree.

Value Stacking

Each grid service performed by a battery may provide some economic value, or benefit, but one service alone may not provide enough value to overcome the lifetime costs of the installation. If a specific scenario allows it, it may be possible to approach multiple grid services with one project to improve a projects economics. Keep in mind, there may be regulatory or technical complications that prevent the a project from attempting multiple stacked services.

One grid service alone may not provide enough value to justify the lifetime costs of an energy storage system. In the right environment, multiple grid services can be stacked to increase the lifetime value.

Understanding Service Compatibility

When value stacking, energy storage service compatibility only flows from bottom up; customer storage may provide distribution and transmission-level services, but transmission storage can NOT provide distribution or customer services.

Reliability vs. Economic Services Reliability services take priority over economic services. For example transmission / distribution deferral services are higher priority than market services.

Local vs. System Level In general, local objectives supersede system objectives when there is a conflict. For example, transmission / distribution deferral is a higher priority than resource adequacy, though operations should be designed such that reliability services never conflict.

Cost Components and Trends

An economic analysis of energy storage systems should clearly articulate what major components are included in the scope of cost. The schematic below shows the major components of an energy storage system. System components consist of batteries, power conversion system, transformer, switchgear, and monitoring and control. A proper economic analysis identifies the costs associated with each of these components.

Source: EPRI. Understanding the components of energy storage systems is a critical first step to understanding energy storage economics.

In addition to identification of major components, there are key BESS services that occur throughout the system's lifetime that need to be accounted for in an economic analysis. The left side of the graphic below shows the beginning of life stacked costs for battery energy storage systems. As shown in the owner's upfront costs, the largest upfront cost is the battery itself. One important consideration, given the significant battery costs, is the sizing assumptions that are used for cost estimates. Often, only a fraction of the procured energy is actually delivered to the customer and some fraction is reserved for safety and performance margins, degradation overbuild, AC/DC losses, or is electrochemically inaccessible. Additionally, the graphic shows relative costs for services throughout BESS operation. These services include operating expenses, fixed system maintenance, and decommissioning and end of life services.

A clear scope of supply is needed to determine owner costs. This includes services and equipment.[1]

Other generation resource costs are often communicated on a $/kW basis, but energy storage has both power and energy components and the normalized cost will vary with duration. This is highlighted in two examples below where it's clear that the longer duration system has a higher cost per kW of power.

  • Source: EPRI. 4 Hour Duration System.
  • Source: EPRI. 2 Hour Duration System.

The image below shows lithium ion cost projections from a 2020 EPRI cost study. As demonstrated in the two examples above, the longer duration systems, as of 2020, are more expensive per kW than the shorter duration systems. However, EPRI's cost study projects that the cost per kW of 8 hour duration lithium ion systems is decreasing at a faster rate than 2 hour lithium ion systems.

Lithium Ion Installed Cost Projections[2]

Modeling Energy Storage

Advanced energy storage is a difficult technology to model owing to its limited energy capacity. Operating an energy storage system now can limit its ability to operate in the future. Additionally, energy storage is not yet a common grid asset and is subject to rapidly changing rules, regulations, and standards. But, the flexibility of energy storage can provide a lot of value when operated well and with consideration for the degradation of the system owing to their ability to go from charging to discharging and vice versa quickly and without interruption. Typically, energy storage systems do not serve just one application and instead leverage their flexibility across several stacked services. Service stacking presents additional modeling challenges, though, because the requirements imposed by each service need to be meet in parallel. The need to ensure a storage system can provide stacked services without running out of stored energy typically necessitates detailed, site-specific time series modeling.

Other Resources

EPRI Tools to Support Valuation Modeling

Reports

Resource Access Level
EPRI Solar Plus Storage Cost Assessment and Design Considerations: Executive Summary (2019) Publicly Available
EPRI Energy Storage Technology and Cost Assessment: Executive Summary (2018) Publicly Available
ESIC Energy Storage Cost Tool and Template Publicly Available
Energy Storage Valuation in California: Policy Planning and Market Information Relevant to the StorageVET Model Publicly Available

References