Difference between revisions of "Energy Storage Product Database/Yotta"
| Line 44: | Line 44: | ||
=Products= | =Products= | ||
Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy. | |||
{| class="wikitable" style="width: 100%; text-align: center;" | {| class="wikitable" style="width: 100%; text-align: center;" | ||
! style="width: 20%" | '''Products''' | ! style="width: 20%" | '''Products''' | ||
Revision as of 16:37, 30 October 2023
| Yotta | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Founded in 2017, Yotta is a designer and developer of integrated solar plus storage solutions for commercial and industrial markets. Originally a microinverter company, their product line has expanded to include LFP energy storage systems, the SolarLEAF; DC-coupled inverters, the dual-power inverter; asset management and reporting software, Yotta Vision; and prefabricated electric vehicle charging structures supported by solar and storage for on- or off-grid contexts and applications, the REV.
History
Yotta Energy was one of seven Caltech Rocket Fund Award recipients in 2020. Yotta also recently received demonstration funding via the CEC BRIDGE awards, focused on building rapid innovation and development to green energy technology.
Deployments
EPRI will be partnering closely with Yotta on this project to deploy, measure, assess, and evaluate the performance and efficacy of their rooftop solar plus storage solution at a multifamily apartment complex in Southern California.
Products
Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy.
| Products | SolarLEAF (SL-1000) | EV Charger |
|---|---|---|
| Industry | Residential, Commercial | Commercial, Industrial |
| Energy Capacity | 14 kWh | 14 kWh |
| Power Capacity | 5 kW | 770 kW |
| Storage | various | various |
| Inverter | Tesla | Tesla |
| Controller | Tesla | Tesla |
Applications
The Powerwall and Powerwall+ are suited for residential and small commercial applications, such as backup power, retail energy time shift on time-of-use rates, demand response, demand charges, and solar self-consumption.[1] [2]
The Powerpack and Megapack are built for large commerical, industrial, and utility applications, such as substation resilience, peak shaving, solar PV ramp limiting, frequency regulation, voltage regulation, volt/VAR control, power quality, resource adaquacy, market participation, investment deferal, etc.[3] [4]
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Self-consumption | yes | yes | yes | |
| Backup Power | yes | yes | yes | yes |
| Energy Time Shift TOU | yes | yes | yes | |
| Peak Shaving | yes | yes | yes | |
| Demand Response | yes | yes | yes | |
| Demand Charge Reduction | yes | yes | yes | yes |
| Solar PV Charging | yes | yes | yes | |
| Solar (renewable) ramp limiting | yes | yes | yes | yes |
| Power Quality | ||||
| Market participation | yes | yes | ||
| Spinning Reserves | yes | |||
| Voltage Regulation | yes | yes | ||
| Frequency Regulation | yes | yes | ||
| Black Start | ||||
| Resource Adequacy Capacity | yes | yes |
Storage System
Tesla sources their battery modules and cells from a variety of manufacturers, partnering with others like Panasonic and Samsung SDI.[5]
Powerwall
Tesla continues being a leading distributor of residential energy storage with the Powerwall solution, which they have begun to released coupled with Tesla solar efforts, alongside continued car sales.
The Powerwall 2.0 is composed of lithium ion battery cells manufactured by Tesla with Gigafactory partner Panasonic. The battery energy storage system generally include within its rectangular enclosure an integrated inverter and thus is AC-coupled by default. In the past some versions did not have a built-in inverter and thus could be DC-coupled. This also allows the system to be quite modular; additional units can be purchased and installed in parallel.
The Powerwall 2.0 sports a total energy capacity of 14 kWh and a usable energy capacity of 13.5 kWh. With a nominal internal DC battery voltage of 50 V, the unit's charge capacity pans out to 280 Ah.
The battery's rated continuous power capacity is 5 kW and the rated peak power capacity is 7 kW. The rated continuous apparent power capacity is 5.8 kVA and the peak apparent power capacity is 7.2 kVA. These values apply for both charge and discharge. Tesla claims a round trip efficiency 90 %.
The value on the specification sheet was derived from the common test condition of 3.3 kW charge/discharge at 25 °C.
The Powerwall 2.0 has been deployed in a number of residential contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia.
The storage system is not always readily available and purchasers should expect delays in procurement as the lithium-ion battery cells used in this product and the same ones used in Tesla vehicles.
Powerpack and Megapack
A single Tesla Powerpack battery energy storage unit consists of sixteen (16) individual battery pods, a thermal control system, and sensor for monitoring and reporting status information of internal components.
The Powerpack 2.0 is composed of lithium ion battery cells manufactured by Tesla with Gigafactory partner Panasonic.
Each Powerpack unit sports an energy capacity of 232 kWh. Each unit's rated continuous power capacity goes up to 130 kW and allows a depth of discharge of 100 %. The round trip efficiency is 88 % for 2-hour systems and 89.5 % for 4-hours systems.
These efficiency calculations were derived from net energy delivered at 25 °C / 77 °F.
The Powerpack 2.0 has been deployed in a number of utility, commercial, and industrial contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia. The EPRI team has played a role in the commissioning and testing of a number of these systems across the country.
Purchasers looking to procure the Powerpack can submit and inquiry to Tesla from their website to receive a follow-up via email or phone.
The Megapack is available in 4-hour and 2-hour options.
Storage System
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Technology Type | Lithium ion | Lithium ion | Lithium ion | Lithium ion |
| Storage Media Provider | various | various | various | various |
| Storage Media Model | Powerwall 2 | Powerwall+ | Powerpack 2.0 Battery Pods | Megapack |
| Coupling Type | AC | AC | AC | |
| Charge Capacity | 280 Ah | |||
| Total Energy | 14 kWh | 14 kWh | 232 kWh | 3,080 kWh |
| Usable Energy | 13.5 kWh | 13.5 kWh | 232 kWh | |
| Rated Continuous Discharge Real Power | 5 kW | 7.6 kW Full sun / 5.8kW no sun | 130 kW | 770 kW |
| Max Peak Discharging Real Power | 7 kW | 9.6 kW off-grid / 5kw on grid | ||
| Rated Continuous Charge Real Power | 5 kW | 7kW | 130 kW | 770 kW |
| Max Peak Charging Real Power | 7 kW | 9.6 kW | ||
| Idle Load | ||||
| Response time | 10 s | 10 s | ||
| DC Voltage (Nominal, Converter Output) | 480 | 480 | ||
| DC Voltage (Range) | 60 - 600 V dc | |||
| DC Voltage (Internal Battery) | 50 V | 50 V | ||
| Rated Continuous Discharge Current | 21 A | 32 A | ||
| Max Peak Discharging Current | 29 A | 40 A | ||
| Rated Continuous Charge Current | 21 A | |||
| Max Peak Charging Current | 29 A | |||
| Roundtrip Efficiency (AC) | 0.9 | 0.9 | 0.88 | 0.94 |
| Roundtrip Efficiency (DC) | 0.918 | 0.9 | ||
| Degradation / Life (cycles) | ||||
| Depth of Discharge | 0.964 | 1 | ||
| Modularity | yes, additional batteries Powerwall unit; hardware above battery is specialized controller | |||
| Test conditions | 25 °C @ 3.3 kW | 25 °C | 25 °C | |
| Cooling System | Internal liquid cooling and heating | Integrated |
Power Conversion System Specifications
Powerwall
The Powerwall 2.0 proprietary battery inverter is internally housed and embedded in the white rectangular packaing of the unit. Because the Powerwall 2.0 comes as an consolidated package with the battery modules and inverter in one enclosure, many of the technical specifications between the two overlap.
Like the battery modules, the inverter is made by Tesla and is internal and proprietary. The rated continuous power capacity is 5 kW and the rated peak power capacity is 7 kW. The rated continuous apparent power capacity is 5.8 kVA and the peak apparent power capacity is 7.2 kVA. These values apply for both charge and discharge. The round trip efficiency is 90 %.
The battery has an overcurrent protection device response at 30 A. The maximum output fault current is 32 A. The maximum supply fault current is 10 kA. The power factor range is +/- 1.0, though drops to +/- 0.85 at full rated power. The system is liquid cooled.[2]
The Powerwall connects to the AC bus in single-phase / split-phase configuration at 120 V / 240 V with nominal frequency of 60 Hz.
The Powerwall 2.0 has been deployed in a number of residential contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia.
As one of its internal components, the inverter can only be acquired as part of the entire Powerwall 2.0 battery energy system.
Powerpack
The Powerpack operates with a bi-directional, power-scalable inverter.
The inverter's power ranges from 70 kVA to 700 kVA at 480 V AC. Its rated AC voltage is three-phase 380 to 480 V AC. The round-trip system efficiency is 88 % for 2-hour systems and 89.5 % for 4-hour systems. Onboard control software allow for communication via Modbus TCP/IP, DNP3, and Rest API. The inverter is housed in an IP66/NEMA 4 rated enclosure, weighing 1120 kg with dimensions of 1044 mm x 1694 mm x 2191 mm.
The Powerpack 2.0 has been deployed in a number of utility, commercial, and industrial contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia. The EPRI team has played a role in the commissioning and testing of a number of these systems across the country.
This inverter is installed in a separate cabinet alongside the Powerpack energy storage system.
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Inverter Make | Tesla | Tesla | Tesla | Tesla |
| Inverter Model | internal | internal | cabinet | |
| Rated AC Continuous Output Real Power | 5 kW | 7.6 kW | ||
| Max AC Peak Output Real Power | 7 kW | 9.6 kW | 130 kW | 1,500kW |
| Idle Load | ||||
| Rated AC Continuous Output Apparent Power | 5.8 kVA | 7.6 kW | ||
| Max AC Peak Output Apparent Power | 7.2 kVA | 9.6 kW | ||
| Rated Reactive Power | ||||
| Rated Continuous Output Current | 21 A | 32 A | ||
| Max Peak Output Current | 29 A | 40 A | ||
| Rated Continuous Battery Input Power | 5 kW | 7 kW | 130 kW | |
| Max Peak Battery Input Power | 7 kW | |||
| Maximum Battery Input Current | ||||
| Maximum Output Fault Current | 32 A | |||
| Overcurrent Protection Device | 30 A | |||
| Maximum Supply Fault Current | 10 kA | |||
| Power Factor Output Range | +/- 1.0 adjustable | +/– 0.9 to 1 | ||
| Power Factor Range (full-rated power) | +/- 0.85 | |||
| Imbalance for Split-Phase Loads | 1 | |||
| Total Harmonic Distortion (THD) | ||||
| Roundtrip Efficiency | 0.9 | 0.975 | 0.87 | |
| AC Connection Type | single-phase / split-phase | single-phase / split-phase | three phase | |
| Nominal Output AC Voltage | 120 V / 240 V | 120 V / 240 V | 380 V to 480 V | |
| Nominal Frequency | 60 Hz | 60 Hz | ||
| Packaging | NEMA 3R | NEMA 3R | outdoor cabinets | Integrated in Megapack container |
| Modularity | yes; scalable inverters from 70 kVA to 700 kVA (at 480V) | |||
| Cooling System | liquid cooling | liquid cooling | internal liquid cooling and heating system |
Energy Management System Specifications
Tesla uses its Opticaster energy management system in the Powerwall, Powerpack, and Megapack to monitor, record, report, and control the battery modules. The Opticaster system seeks to forecast and control energy storage systems in real-time.[6]
The Powerwall's energy storage system is self-managed by Tesla themselves and is able to integrate with Tesla-installed solar at the same site as well. The makes the user experience relatively seamless when compared to comparable systems that rely on a variety of energy monitoring systems and sources. Tesla however is also known for not releasing a public API for their battery and solar data, thus making it virtually impossible to connect Tesla data with other energy monitoring and management systems apart from installing another distinct hardware kit for battery and solar monitoring.
The Tesla app, accessible via web or mobile device, allows users to manage their battery system for Backup power, solar PV self-consumption, and time-based control. The battery must be constantly connected to the Internet via Ethernet cable or Wi-Fi to enable such control. No direct offline control via MODBUS or other control protocols are available at this time.
Selected customer testimonials include mention of utilizing the Tesla Powerpacks for site-specific as well as general applications such as network support, diesel abatement, renewable consumption, peak shaving, capacity reserve, demand response, and load shifting. Onboard control software allow for communication via Modbus TCP/IP, DNP3, and Rest API.
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Energy Management System | Tesla | Tesla | Tesla | Tesla |
| Control Capabilities | Backup power, solar PV self-consumption, time-based control, off-grid capability (coming soon) | Backup power, solar PV self-consumption, time-based control, off-grid capability | Peak shaving, load shifting, emergency backup, demand response, renewable integration, capacity reserve, ancillary services, T&D support | |
| Portal availability | Monitoring and control functions available on web / mobile device Tesla app | Monitoring and control functions available on web / mobile device Tesla app | ||
| Communications & Network | Ethernet, WiFi | Ethernet, Wi-Fi, cellular LTE 4G | Modbus TCP/IP; DNP3 |
Environment and Mechanical
The Powerwall 2.0 is offered in its well-known sleek white rectangular enclosures. The HxWxD dimensions are 1150 mm x 755 mm x 155 mm and weighs 114 kg. The battery unit can be mounted on a wall or on the ground. It can be installed either outdoor or indoor. The NEMA 3R enclosure has an ingress rating of IP 67 for the battery and power electronics and IP 56 for wiring.
The operating temperature ranges from -20 to 50 °C with an optimal temperature range of 0 to 30 °C. The unit is rated for wet locations, can run in an operating humidity of 100 % relative humidity condensing and at an altitude of up to 3000 m. The system is modular and additional units can be installed in parallel.
The Powerpack system comes in various outdoor, metal cabinets and enclosures. Batteries are housed in an IP35/NEMA 3R rated enclosure, weighing 2199 kg with dimensions of 1317 mm x 968 mm x 2187 mm. The inverter is housed in an IP66/NEMA 4 rated enclosure, weighing 1120 kg with dimensions of 1044 mm x 1694 mm x 2191 mm.
The operating temperature ranges from -30 °C to 50 °C or -22 °F to 122 °F. The unit is rated for wet locations, can run in an operating humidity of 100 % relative humidity condensing and at an altitude of up to 3000 m. The system is modular and additional units can be installed in parallel.
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Mounting | Floor or Wall | Floor or Wall | Floor Cabinet | Floor Cabinet |
| Weight | 125 kg | 140 kg | 2,199 kg (battery)
1,120 kg (inverter) |
30,500 kg max (67,100 lbs max) |
| Footprint | 1150 mm x 753 mm x 147 mm (45.3 x 29.6 x 5.75 in) | 1596 x 755 x 160 mm (62.8 x 29.7 x 6.3 in) | 1317 mm x 968 mm x 2187 mm (battery)
1044 mm x 1394 mm x 2191 mm (inverter) |
7.26 m L x 1.7 m D x 2.5 m H (23.8 ft L x 5.42 ft D x 8.3 ft H) |
| Indoor/outdoor | Indoor or Outdoor | Indoor or Outdoor | Outdoor | Outdoor |
| Enclosure | NEMA 3R | NEMA 3R | Powerpack: NEMA 3R
Inverter: NEMA 4 |
|
| Ingress Rating | IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) | IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) | Pods: IP67
Powerpack: IP35 Inverter: IP66 |
|
| Noise | < 40 dB at 30 °C | < 40 dB optimal, < 50 db max @ 1 m | ||
| Operating temperature | -20 to 50° °C | -20 to 50° °C | -30 °C to 50 °C | |
| Optimum temperature | 0 °C to 30° °C | 0 °C to 30° °C | ||
| Operating humidity | 100% relative humidity, condensing | 100% relative humidity, condensing | ||
| Altitude | < 3000 m | < 3000 m | ||
| Modularity | Powerpacks can be added to create a larger effective storage system |
Warranty
Tesla’s 2020 Megapack datasheet specifies “a standard warranty of up to 15 years, with the option of a 20-year Capacity Maintenance Agreement (CMA) in certain cases.” Tesla’s “Megapack Order Agreement” refers to a “Megapack Manufacturer’s Limited Warranty” document that is not publicly available.
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| System Warranty | 10 years | 10 years | 15 year, limited | 15 year standard / 20 year with capacity agreement |
| Battery Warranty | ||||
| Inverter Warranty |
Codes, Standards, and Regulations
| Powerwall 2 | Powerwall+ | Powerpack 2.0 | Megapack | |
|---|---|---|---|---|
| Safety | Rated for wet locations | Rated for wet locations, integrated arc fault circuit interuptor, rapid shutdown | ||
| AC 156 | yes | yes | ||
| FCC CFR Part 15, Class B | yes | yes | ||
| ICES 003 | yes | |||
| IEEE 519 | yes | |||
| IEEE 1547 | yes | |||
| IEEE 1547A | yes | |||
| IEEE 62.41.2 | yes | |||
| IEEE 693-2005 | yes | |||
| REACH | yes | |||
| RoHS Directive 2011/65/EU | yes | |||
| UL 1623 | yes | |||
| UL 1642 | yes | yes | ||
| UL 1699B | yes | |||
| UL 1741 | yes | yes | yes | yes |
| UL 1741SA | yes | |||
| UL 1778 | yes | |||
| UL 1973 | yes | yes | yes | yes |
| UL 60950-1 | yes | |||
| UL 9540 | yes | yes | yes | |
| UL 9540A | yes | yes | ||
| UN 38.3 | yes |