Difference between revisions of "Energy Storage Product Database/Yotta"

From EPRI Storage Wiki
Jump to navigation Jump to search
Line 147: Line 147:


==Storage System==
==Storage System==
Tesla sources their battery modules and cells from a variety of manufacturers, partnering with others like Panasonic and Samsung SDI.<ref name="tesla-battery-cell-source">[https://www.energy-storage.news/tesla-using-samsung-cells-in-south-australia-as-100-days-countdown-begins/ Energy Storage New web article]</ref>


===Powerwall===
===SolarLEAF===
Tesla continues being a leading distributor of residential energy storage with the Powerwall solution, which they have begun to released coupled with Tesla solar efforts, alongside continued car sales.


The Powerwall 2.0 is composed of lithium ion battery cells manufactured by Tesla with Gigafactory partner Panasonic. The battery energy storage system generally include within its rectangular enclosure an integrated inverter and thus is AC-coupled by default. In the past some versions did not have a built-in inverter and thus could be DC-coupled. This also allows the system to be quite modular; additional units can be purchased and installed in parallel.


The Powerwall 2.0 sports a total energy capacity of 14 kWh and a usable energy capacity of 13.5 kWh. With a nominal internal DC battery voltage of 50 V, the unit's charge capacity pans out to 280 Ah.
===REV===


The battery's rated continuous power capacity is 5 kW and the rated peak power capacity is 7 kW. The rated continuous apparent power capacity is 5.8 kVA and the peak apparent power capacity is 7.2 kVA. These values apply for both charge and discharge. Tesla claims a round trip efficiency 90 %.
The value on the specification sheet was derived from the common test condition of 3.3 kW charge/discharge at 25 °C.
The Powerwall 2.0 has been deployed in a number of residential contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia.
The storage system is not always readily available and purchasers should expect delays in procurement as the lithium-ion battery cells used in this product and the same ones used in Tesla vehicles.
===Powerpack and Megapack===
A single Tesla Powerpack battery energy storage unit consists of sixteen (16) individual battery pods, a thermal control system, and sensor for monitoring and reporting status information of internal components.
The Powerpack 2.0 is composed of lithium ion battery cells manufactured by Tesla with Gigafactory partner Panasonic.
Each Powerpack unit sports an energy capacity of 232 kWh. Each unit's rated continuous power capacity goes up to 130 kW and allows a depth of discharge of 100 %. The round trip efficiency is 88 % for 2-hour systems and 89.5 % for 4-hours systems.
These efficiency calculations were derived from net energy delivered at 25 °C / 77 °F.
The Powerpack 2.0 has been deployed in a number of utility, commercial, and industrial contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia. The EPRI team has played a role in the commissioning and testing of a number of these systems across the country.
Purchasers looking to procure the Powerpack can submit and inquiry to Tesla from their website to receive a follow-up via email or phone.
The Megapack is available in 4-hour and 2-hour options.
==Storage System==
==Storage System==
{| class="wikitable  mw-collapsible" style="width: 100%; text-align: center;"
{| class="wikitable  mw-collapsible" style="width: 100%; text-align: center;"

Revision as of 17:34, 30 October 2023

Yotta
Products SolarLeaf REV
Industry Residential Commercial, Industrial
Energy Capacity 1 kWh 232 kWh
Power Capacity 675 W 130 kW
Storage Murata Murata
Inverter Yotta Yotta
Controller Yotta Yotta

Founded in 2017, Yotta is a designer and developer of integrated solar plus storage solutions for commercial and industrial markets. Originally a microinverter company, their product line has expanded to include LFP energy storage systems, the SolarLEAF; DC-coupled inverters, the dual-power inverter; asset management and reporting software, Yotta Vision; and prefabricated electric vehicle charging structures supported by solar and storage for on- or off-grid contexts and applications, the REV.

History

Yotta Energy was one of seven Caltech Rocket Fund Award recipients in 2020. Yotta also recently received demonstration funding via the CEC BRIDGE awards, focused on building rapid innovation and development to green energy technology.

Deployments

EPRI will be partnering closely with Yotta on this project to deploy, measure, assess, and evaluate the performance and efficacy of their rooftop solar plus storage solution at a multifamily apartment complex in Southern California.

Products

Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy. Though this increases the length of cable needed for wiring up an installation, each individual battery module can be easily carried, since the overall weight is spread out over a large number of units. The SolarLEAF is designed with passive thermal regulation technology that allows the systems to withstand being installed on top of hot roofs.

The REV is a deployable EV charging system equipped with solar panels, battery energy storage, power inverters, and EV charging ports. It is meant to provide an off-grid EV charging solution to locations that cannot be serviced by grid-tied power.

Yotta is reported to source its lithium iron phosphate batteries from Murata and their Fortelion line of energy storage cells.

Products SolarLEAF (SL-1000) REV
Industry Residential, Commercial Commercial, Industrial
Energy Capacity 14 kWh 14 kWh
Power Capacity 5 kW 770 kW
Storage various various
Inverter Tesla Tesla
Controller Tesla Tesla

Applications

SolarLEAF REV
Self-consumption yes yes
Backup Power yes yes
Energy Time Shift TOU yes yes
Peak Shaving yes yes
Demand Response yes yes
Demand Charge Reduction yes yes
Solar PV Charging yes yes
Solar (renewable) ramp limiting yes yes
Power Quality
Market participation
Spinning Reserves
Voltage Regulation
Frequency Regulation
Black Start
Resource Adequacy Capacity

Storage System

SolarLEAF

REV

Storage System

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Technology Type Lithium ion Lithium ion Lithium ion Lithium ion
Storage Media Provider various various various various
Storage Media Model Powerwall 2 Powerwall+ Powerpack 2.0 Battery Pods Megapack
Coupling Type AC AC AC
Charge Capacity 280 Ah
Total Energy 14 kWh 14 kWh 232 kWh 3,080 kWh
Usable Energy 13.5 kWh 13.5 kWh 232 kWh
Rated Continuous Discharge Real Power 5 kW 7.6 kW Full sun / 5.8kW no sun 130 kW 770 kW
Max Peak Discharging Real Power 7 kW 9.6 kW off-grid / 5kw on grid
Rated Continuous Charge Real Power 5 kW 7kW 130 kW 770 kW
Max Peak Charging Real Power 7 kW 9.6 kW
Idle Load
Response time 10 s 10 s
DC Voltage (Nominal, Converter Output) 480 480
DC Voltage (Range) 60 - 600 V dc
DC Voltage (Internal Battery) 50 V 50 V
Rated Continuous Discharge Current 21 A 32 A
Max Peak Discharging Current 29 A 40 A
Rated Continuous Charge Current 21 A
Max Peak Charging Current 29 A
Roundtrip Efficiency (AC) 0.9 0.9 0.88 0.94
Roundtrip Efficiency (DC) 0.918 0.9
Degradation / Life (cycles)
Depth of Discharge 0.964 1
Modularity yes, additional batteries Powerwall unit; hardware above battery is specialized controller
Test conditions 25 °C @ 3.3 kW 25 °C 25 °C
Cooling System Internal liquid cooling and heating Integrated

Power Conversion System Specifications

Powerwall

The Powerwall 2.0 proprietary battery inverter is internally housed and embedded in the white rectangular packaing of the unit. Because the Powerwall 2.0 comes as an consolidated package with the battery modules and inverter in one enclosure, many of the technical specifications between the two overlap.

Like the battery modules, the inverter is made by Tesla and is internal and proprietary. The rated continuous power capacity is 5 kW and the rated peak power capacity is 7 kW. The rated continuous apparent power capacity is 5.8 kVA and the peak apparent power capacity is 7.2 kVA. These values apply for both charge and discharge. The round trip efficiency is 90 %.

The battery has an overcurrent protection device response at 30 A. The maximum output fault current is 32 A. The maximum supply fault current is 10 kA. The power factor range is +/- 1.0, though drops to +/- 0.85 at full rated power. The system is liquid cooled.[2]

The Powerwall connects to the AC bus in single-phase / split-phase configuration at 120 V / 240 V with nominal frequency of 60 Hz.

The Powerwall 2.0 has been deployed in a number of residential contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia.

As one of its internal components, the inverter can only be acquired as part of the entire Powerwall 2.0 battery energy system.

Powerpack

The Powerpack operates with a bi-directional, power-scalable inverter.

The inverter's power ranges from 70 kVA to 700 kVA at 480 V AC. Its rated AC voltage is three-phase 380 to 480 V AC. The round-trip system efficiency is 88 % for 2-hour systems and 89.5 % for 4-hour systems. Onboard control software allow for communication via Modbus TCP/IP, DNP3, and Rest API. The inverter is housed in an IP66/NEMA 4 rated enclosure, weighing 1120 kg with dimensions of 1044 mm x 1694 mm x 2191 mm.

The Powerpack 2.0 has been deployed in a number of utility, commercial, and industrial contexts in a variety of climates and locations, utility services territories, and countries, though primarily in the United States and Australia. The EPRI team has played a role in the commissioning and testing of a number of these systems across the country.

This inverter is installed in a separate cabinet alongside the Powerpack energy storage system.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Inverter Make Tesla Tesla Tesla Tesla
Inverter Model internal internal cabinet
Rated AC Continuous Output Real Power 5 kW 7.6 kW
Max AC Peak Output Real Power 7 kW 9.6 kW 130 kW 1,500kW
Idle Load
Rated AC Continuous Output Apparent Power 5.8 kVA 7.6 kW
Max AC Peak Output Apparent Power 7.2 kVA 9.6 kW
Rated Reactive Power
Rated Continuous Output Current 21 A 32 A
Max Peak Output Current 29 A 40 A
Rated Continuous Battery Input Power 5 kW 7 kW 130 kW
Max Peak Battery Input Power 7 kW
Maximum Battery Input Current
Maximum Output Fault Current 32 A
Overcurrent Protection Device 30 A
Maximum Supply Fault Current 10 kA
Power Factor Output Range +/- 1.0 adjustable +/– 0.9 to 1
Power Factor Range (full-rated power) +/- 0.85
Imbalance for Split-Phase Loads 1
Total Harmonic Distortion (THD)
Roundtrip Efficiency 0.9 0.975 0.87
AC Connection Type single-phase / split-phase single-phase / split-phase three phase
Nominal Output AC Voltage 120 V / 240 V 120 V / 240 V 380 V to 480 V
Nominal Frequency 60 Hz 60 Hz
Packaging NEMA 3R NEMA 3R outdoor cabinets Integrated in Megapack container
Modularity yes; scalable inverters from 70 kVA to 700 kVA (at 480V)
Cooling System liquid cooling liquid cooling internal liquid cooling and heating system 

Energy Management System Specifications

Tesla uses its Opticaster energy management system in the Powerwall, Powerpack, and Megapack to monitor, record, report, and control the battery modules. The Opticaster system seeks to forecast and control energy storage systems in real-time.[1]

The Powerwall's energy storage system is self-managed by Tesla themselves and is able to integrate with Tesla-installed solar at the same site as well. The makes the user experience relatively seamless when compared to comparable systems that rely on a variety of energy monitoring systems and sources. Tesla however is also known for not releasing a public API for their battery and solar data, thus making it virtually impossible to connect Tesla data with other energy monitoring and management systems apart from installing another distinct hardware kit for battery and solar monitoring.

The Tesla app, accessible via web or mobile device, allows users to manage their battery system for Backup power, solar PV self-consumption, and time-based control. The battery must be constantly connected to the Internet via Ethernet cable or Wi-Fi to enable such control. No direct offline control via MODBUS or other control protocols are available at this time.

Selected customer testimonials include mention of utilizing the Tesla Powerpacks for site-specific as well as general applications such as network support, diesel abatement, renewable consumption, peak shaving, capacity reserve, demand response, and load shifting. Onboard control software allow for communication via Modbus TCP/IP, DNP3, and Rest API.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Energy Management System Tesla Tesla Tesla Tesla
Control Capabilities Backup power, solar PV self-consumption, time-based control, off-grid capability (coming soon) Backup power, solar PV self-consumption, time-based control, off-grid capability Peak shaving, load shifting, emergency backup, demand response, renewable integration, capacity reserve, ancillary services, T&D support
Portal availability Monitoring and control functions available on web / mobile device Tesla app Monitoring and control functions available on web / mobile device Tesla app
Communications & Network Ethernet, WiFi Ethernet, Wi-Fi, cellular LTE 4G Modbus TCP/IP; DNP3

Environment and Mechanical

The Powerwall 2.0 is offered in its well-known sleek white rectangular enclosures. The HxWxD dimensions are 1150 mm x 755 mm x 155 mm and weighs 114 kg. The battery unit can be mounted on a wall or on the ground. It can be installed either outdoor or indoor. The NEMA 3R enclosure has an ingress rating of IP 67 for the battery and power electronics and IP 56 for wiring.

The operating temperature ranges from -20 to 50 °C with an optimal temperature range of 0 to 30 °C. The unit is rated for wet locations, can run in an operating humidity of 100 % relative humidity condensing and at an altitude of up to 3000 m. The system is modular and additional units can be installed in parallel.

The Powerpack system comes in various outdoor, metal cabinets and enclosures. Batteries are housed in an IP35/NEMA 3R rated enclosure, weighing 2199 kg with dimensions of 1317 mm x 968 mm x 2187 mm. The inverter is housed in an IP66/NEMA 4 rated enclosure, weighing 1120 kg with dimensions of 1044 mm x 1694 mm x 2191 mm.

The operating temperature ranges from -30 °C to 50 °C or -22 °F to 122 °F. The unit is rated for wet locations, can run in an operating humidity of 100 % relative humidity condensing and at an altitude of up to 3000 m. The system is modular and additional units can be installed in parallel.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Mounting Floor or Wall Floor or Wall Floor Cabinet Floor Cabinet
Weight 125 kg 140 kg 2,199 kg (battery)

1,120 kg (inverter)

30,500 kg max (67,100 lbs max)
Footprint 1150 mm x 753 mm x 147 mm (45.3 x 29.6 x 5.75 in) 1596 x 755 x 160 mm (62.8 x 29.7 x 6.3 in) 1317 mm x 968 mm x 2187 mm (battery)

1044 mm x 1394 mm x 2191 mm (inverter)

7.26 m L x 1.7 m D x 2.5 m H (23.8 ft L x 5.42 ft D x 8.3 ft H)
Indoor/outdoor Indoor or Outdoor Indoor or Outdoor Outdoor Outdoor
Enclosure NEMA 3R NEMA 3R Powerpack: NEMA 3R

Inverter: NEMA 4

Ingress Rating IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) Pods: IP67

Powerpack: IP35 Inverter: IP66

Noise < 40 dB at 30 °C < 40 dB optimal, < 50 db max @ 1 m
Operating temperature -20 to 50° °C -20 to 50° °C -30 °C to 50 °C
Optimum temperature 0 °C to 30° °C 0 °C to 30° °C
Operating humidity 100% relative humidity, condensing 100% relative humidity, condensing
Altitude < 3000 m < 3000 m
Modularity Powerpacks can be added to create a larger effective storage system

Warranty

Tesla’s 2020 Megapack datasheet specifies “a standard warranty of up to 15 years, with the option of a 20-year Capacity Maintenance Agreement (CMA) in certain cases.” Tesla’s “Megapack Order Agreement” refers to a “Megapack Manufacturer’s Limited Warranty” document that is not publicly available.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
System Warranty 10 years 10 years 15 year, limited 15 year standard / 20 year with capacity agreement
Battery Warranty
Inverter Warranty

Codes, Standards, and Regulations

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Safety Rated for wet locations Rated for wet locations, integrated arc fault circuit interuptor, rapid shutdown
AC 156 yes yes
FCC CFR Part 15, Class B yes yes
ICES 003 yes
IEEE 519 yes
IEEE 1547 yes
IEEE 1547A yes
IEEE 62.41.2 yes
IEEE 693-2005 yes
REACH yes
RoHS Directive 2011/65/EU yes
UL 1623 yes
UL 1642 yes yes
UL 1699B yes
UL 1741 yes yes yes yes
UL 1741SA yes
UL 1778 yes
UL 1973 yes yes yes yes
UL 60950-1 yes
UL 9540 yes yes yes
UL 9540A yes yes
UN 38.3 yes

References