Difference between revisions of "Energy Storage Product Database/Yotta"

From EPRI Storage Wiki
Jump to navigation Jump to search
Line 616: Line 616:
{| class="wikitable  mw-collapsible" style="width: 100%; text-align: center;"
{| class="wikitable  mw-collapsible" style="width: 100%; text-align: center;"
! style="width: 20%" |  
! style="width: 20%" |  
! style="width: 20%" | Powerwall 2
! style="width: 40%" | Hybrid E5
! style="width: 20%" | Powerwall+
! style="width: 40%" | Battery Energy Storage Cabinet
! style="width: 20%" | Powerpack 2.0
! style="width: 20%" | Megapack
|-
|-
| ''System Warranty''
| ''System Warranty''
| 10 years
|  
| 10 years
|  
| 15 year, limited
| 15 year standard / 20 year with capacity agreement
|-
|-
| ''Battery Warranty''
| ''Battery Warranty''
|  
| 5 years / 12.6 MWh
|
|
|  
|  
|-
|-
| ''Inverter Warranty''
| ''Inverter Warranty''
|
|
|  
|  
|  
|  

Revision as of 18:35, 30 October 2023

Yotta
Products SolarLeaf REV
Industry Residential Commercial, Industrial
Energy Capacity 1 kWh 500 kWh
Power Capacity 0.675 kW 24 kW
Storage Murata Murata
Inverter Yotta Yotta
Controller Yotta Yotta

Founded in 2017, Yotta is a designer and developer of integrated solar plus storage solutions for commercial and industrial markets. Originally a microinverter company, their product line has expanded to include LFP energy storage systems, the SolarLEAF; DC-coupled inverters, the dual-power inverter; asset management and reporting software, Yotta Vision; and prefabricated electric vehicle charging structures supported by solar and storage for on- or off-grid contexts and applications, the REV.

History

Yotta Energy was one of seven Caltech Rocket Fund Award recipients in 2020. Yotta also recently received demonstration funding via the CEC BRIDGE awards, focused on building rapid innovation and development to green energy technology.

Deployments

EPRI will be partnering closely with Yotta on this project to deploy, measure, assess, and evaluate the performance and efficacy of their rooftop solar plus storage solution at a multifamily apartment complex in Southern California.

Products

SolarLEAF

Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy. Though this increases the length of cable needed for wiring up an installation, each individual battery module can be easily carried, since the overall weight is spread out over a large number of units. The SolarLEAF is designed with passive thermal regulation technology that allows the systems to withstand being installed on top of hot roofs.

REV

The REV is a deployable EV charging system equipped with solar panels, battery energy storage, power inverters, and EV charging ports. It is meant to provide an off-grid EV charging solution to locations that cannot be serviced by grid-tied power. The battery energy capacity of the system is configurable from 50 to 300 kWh and its EV charging power capacity tops out at 24 kW. The REV is can be connected to the grid, but is also able to run off-grid, with its solar PV system, expandable from 15 to 50 kW.

Products SolarLEAF (SL-1000) REV
Industry Residential, Commercial Commercial, Industrial
Energy Capacity 14 kWh 14 kWh
Power Capacity 5 kW 770 kW
Storage various various
Inverter Tesla Tesla
Controller Tesla Tesla

Applications

SolarLEAF REV
Self-consumption yes yes
Backup Power yes yes
Energy Time Shift TOU yes
Peak Shaving yes yes
Demand Response yes
Demand Charge Reduction yes
Solar PV Charging yes yes
Solar (renewable) ramp limiting yes yes
Power Quality yes
Market participation
Spinning Reserves
Voltage Regulation
Frequency Regulation
Black Start
Resource Adequacy Capacity

Storage System

Yotta is reported to source its lithium iron phosphate batteries from Murata and their Fortelion line of energy storage cells.

Storage System

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Technology Type Lithium ion Lithium ion Lithium ion Lithium ion
Storage Media Provider various various various various
Storage Media Model Powerwall 2 Powerwall+ Powerpack 2.0 Battery Pods Megapack
Coupling Type AC AC AC
Charge Capacity 280 Ah
Total Energy 14 kWh 14 kWh 232 kWh 3,080 kWh
Usable Energy 13.5 kWh 13.5 kWh 232 kWh
Rated Continuous Discharge Real Power 5 kW 7.6 kW Full sun / 5.8kW no sun 130 kW 770 kW
Max Peak Discharging Real Power 7 kW 9.6 kW off-grid / 5kw on grid
Rated Continuous Charge Real Power 5 kW 7kW 130 kW 770 kW
Max Peak Charging Real Power 7 kW 9.6 kW
Idle Load
Response time 10 s 10 s
DC Voltage (Nominal, Converter Output) 480 480
DC Voltage (Range) 60 - 600 V dc
DC Voltage (Internal Battery) 50 V 50 V
Rated Continuous Discharge Current 21 A 32 A
Max Peak Discharging Current 29 A 40 A
Rated Continuous Charge Current 21 A
Max Peak Charging Current 29 A
Roundtrip Efficiency (AC) 0.9 0.9 0.88 0.94
Roundtrip Efficiency (DC) 0.918 0.9
Degradation / Life (cycles)
Depth of Discharge 0.964 1
Modularity yes, additional batteries Powerwall unit; hardware above battery is specialized controller
Test conditions 25 °C @ 3.3 kW 25 °C 25 °C
Cooling System Internal liquid cooling and heating Integrated

Power Conversion System Specifications

The Yotta dual power mircoinverter (DPI) is installed alongside and connected to the SolarLEAF and also mounted underneath solar PV panels. The inverter is three-phase and can accept four inputs of solar PV panels or SolarLEAF. It is available in two different output voltage levels, the DPI-208 for 208 volts and the DPI-480 for 480 volts.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Inverter Make Tesla Tesla Tesla Tesla
Inverter Model internal internal cabinet
Rated AC Continuous Output Real Power 5 kW 7.6 kW
Max AC Peak Output Real Power 7 kW 9.6 kW 130 kW 1,500kW
Idle Load
Rated AC Continuous Output Apparent Power 5.8 kVA 7.6 kW
Max AC Peak Output Apparent Power 7.2 kVA 9.6 kW
Rated Reactive Power
Rated Continuous Output Current 21 A 32 A
Max Peak Output Current 29 A 40 A
Rated Continuous Battery Input Power 5 kW 7 kW 130 kW
Max Peak Battery Input Power 7 kW
Maximum Battery Input Current
Maximum Output Fault Current 32 A
Overcurrent Protection Device 30 A
Maximum Supply Fault Current 10 kA
Power Factor Output Range +/- 1.0 adjustable +/– 0.9 to 1
Power Factor Range (full-rated power) +/- 0.85
Imbalance for Split-Phase Loads 1
Total Harmonic Distortion (THD)
Roundtrip Efficiency 0.9 0.975 0.87
AC Connection Type single-phase / split-phase single-phase / split-phase three phase
Nominal Output AC Voltage 120 V / 240 V 120 V / 240 V 380 V to 480 V
Nominal Frequency 60 Hz 60 Hz
Packaging NEMA 3R NEMA 3R outdoor cabinets Integrated in Megapack container
Modularity yes; scalable inverters from 70 kVA to 700 kVA (at 480V)
Cooling System liquid cooling liquid cooling internal liquid cooling and heating system 

Energy Management System Specifications

Yotta's energy management system is Yotta Vision that provides users with data analytics and visibility into their system.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Energy Management System Tesla Tesla Tesla Tesla
Control Capabilities Backup power, solar PV self-consumption, time-based control, off-grid capability (coming soon) Backup power, solar PV self-consumption, time-based control, off-grid capability Peak shaving, load shifting, emergency backup, demand response, renewable integration, capacity reserve, ancillary services, T&D support
Portal availability Monitoring and control functions available on web / mobile device Tesla app Monitoring and control functions available on web / mobile device Tesla app
Communications & Network Ethernet, WiFi Ethernet, Wi-Fi, cellular LTE 4G Modbus TCP/IP; DNP3

Environment and Mechanical

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Mounting Floor or Wall Floor or Wall Floor Cabinet Floor Cabinet
Weight 125 kg 140 kg 2,199 kg (battery)

1,120 kg (inverter)

30,500 kg max (67,100 lbs max)
Footprint 1150 mm x 753 mm x 147 mm (45.3 x 29.6 x 5.75 in) 1596 x 755 x 160 mm (62.8 x 29.7 x 6.3 in) 1317 mm x 968 mm x 2187 mm (battery)

1044 mm x 1394 mm x 2191 mm (inverter)

7.26 m L x 1.7 m D x 2.5 m H (23.8 ft L x 5.42 ft D x 8.3 ft H)
Indoor/outdoor Indoor or Outdoor Indoor or Outdoor Outdoor Outdoor
Enclosure NEMA 3R NEMA 3R Powerpack: NEMA 3R

Inverter: NEMA 4

Ingress Rating IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) IP 67 (Battery and Power Electronics), IP 56 (Wiring Compartment) Pods: IP67

Powerpack: IP35 Inverter: IP66

Noise < 40 dB at 30 °C < 40 dB optimal, < 50 db max @ 1 m
Operating temperature -20 to 50° °C -20 to 50° °C -30 °C to 50 °C
Optimum temperature 0 °C to 30° °C 0 °C to 30° °C
Operating humidity 100% relative humidity, condensing 100% relative humidity, condensing
Altitude < 3000 m < 3000 m
Modularity Powerpacks can be added to create a larger effective storage system

Warranty

Hybrid E5 Battery Energy Storage Cabinet
System Warranty
Battery Warranty 5 years / 12.6 MWh
Inverter Warranty

Codes, Standards, and Regulations

Hybrid E5 Battery Energy Storage Cabinet
CPUC Rule 21 pending
FCC CFR Part 15 Class A pending
HECO Rule 14 yes
IEC 60950 yes
IEC 61000-6-2 yes
IEC 62040-1 yes
IEC 62109-1 yes
IEC 62116 yes
IEEE 1547 compliant, pending
UL 1741 pending
UL 1741SA pending
UL 1973 yes
UN 38.3 yes yes

References