Difference between revisions of "Energy Storage Product Database/Yotta"

From EPRI Storage Wiki
Jump to navigation Jump to search
Line 268: Line 268:
{| class="wikitable  mw-collapsible mw-collapsed" style="width: 100%; text-align: center;"
{| class="wikitable  mw-collapsible mw-collapsed" style="width: 100%; text-align: center;"
! style="width: 20%" |  
! style="width: 20%" |  
! style="width: 20%" | Powerwall 2
! style="width: 40%" | Hybrid E5
! style="width: 20%" | Powerwall+
! style="width: 40%" | Battery Energy Storage Cabinet
! style="width: 20%" | Powerpack 2.0
! style="width: 20%" | Megapack
|-
|-
| ''Inverter Make''
| ''Inverter Make''
| Tesla
| Delta
| Tesla
| Delta
| Tesla
| Tesla
|-
|-
| ''Inverter Model''
| ''Inverter Model''
| internal
| E5
| internal
| Power Conditioning System
| cabinet
|  
|-
|-
| ''Rated AC Continuous Output Real Power''
| ''Rated AC Continuous Output Real Power''
| 5 kW
| 5 kW
| 7.6 kW
| 125 kW
|-
| ''Max AC Peak Output Real Power''
|  
|  
|  
|  
|-
| ''Max AC Peak Output Real Power''
| 7 kW
| 9.6 kW
| 130 kW
| 1,500kW
|-
|-
| ''Idle Load''
| ''Idle Load''
|  
| 30 W
|  
| < 20 W
|
|
|-
|-
| ''Rated AC Continuous Output Apparent Power''
| ''Rated AC Continuous Output Apparent Power''
| 5.8 kVA
| 5 kVA
| 7.6 kW
| 125 kVA
|
|
|-
|-
| ''Max AC Peak Output Apparent Power''
| ''Max AC Peak Output Apparent Power''
| 7.2 kVA
| 9.6 kW
|  
|  
|  
|  
|-
|-
| ''Rated Reactive Power''
| ''Rated Reactive Power''
|
|
|  
|  
|  
|  
|-
|-
| ''Rated Continuous Output Current''
| ''Rated Continuous Output Current''
| 21 A
| 32 A
|
|  
|  
| 150.4 A (linear load), 120 A (non-linear)
|-
|-
| ''Max Peak Output Current''
| ''Max Peak Output Current''
| 29 A
| 40 A
|
|  
|  
| 167 A
|-
|-
| ''Rated Continuous Battery Input Power''
| ''Rated Continuous Battery Input Power''
| 5 kW
| 7 kW
| 130 kW
|  
|  
| 122 kW
|-
|-
| ''Max Peak Battery Input Power''
| ''Max Peak Battery Input Power''
| 7 kW
|
|  
|  
|  
|  
Line 347: Line 321:
| ''Maximum Battery Input Current''
| ''Maximum Battery Input Current''
|  
|  
|  
| 163 A
|
|
|-
|-
| ''Maximum Output Fault Current''
| ''Maximum Output Fault Current''
| 32 A
|
|  
|  
|  
|  
|-
|-
| ''Overcurrent Protection Device''
| ''Overcurrent Protection Device''
| 30 A
|
|  
|  
|  
|  
|-
|-
| ''Maximum Supply Fault Current''
| ''Maximum Supply Fault Current''
| 10 kA
|
|  
|  
|  
|  
|-
|-
| ''Power Factor Output Range''
| ''Power Factor Output Range''
| +/- 1.0 adjustable
| 0.8 leading to 0.8 lagging
| +/– 0.9 to 1
| adjust from -1 to 1
|
|
|-
|-
| ''Power Factor Range (full-rated power)''
| ''Power Factor Range (full-rated power)''
| +/- 0.85
|
|  
|  
|  
|  
|-
|-
| ''Imbalance for Split-Phase Loads''
| ''Imbalance for Split-Phase Loads''
| 1
|
|  
|  
|  
|  
|-
|-
| ''Total Harmonic Distortion (THD)''
| ''Total Harmonic Distortion (THD)''
|  
| < 3% at rated power
|  
| < 5% at rated power
|
|
|-
|-
| ''Roundtrip Efficiency''
| ''Roundtrip Efficiency''
| 0.9
| 0.972
| 0.975
| 97.8% (peak)
| 0.87
97.5% (CEC)
|
|-
|-
| ''AC Connection Type''
| ''AC Connection Type''
| single-phase / split-phase
| single-phase
| single-phase / split-phase
| three-phase, three-wire or four-wire
| three phase
|
|-
|-
| ''Nominal Output AC Voltage''
| ''Nominal Output AC Voltage''
| 120 V / 240 V
| 230 V
| 120 V / 240 V
| 480 V
| 380 V to 480 V
|
|-
|-
| ''Nominal Frequency''
| ''Nominal Frequency''
| 60 Hz
| 60 Hz
| 60 Hz
| 60 Hz
|
|
|-
|-
| ''Packaging''
| ''Packaging''
| NEMA 3R
| IP 65
| NEMA 3R
|  
| outdoor cabinets
| Integrated in Megapack container
|-
|-
| ''Modularity''
| ''Modularity''
|  
|  
|
| yes; scalable inverters from 70 kVA to 700 kVA (at 480V)
|  
|  
|-
|-
| ''Cooling System''
| ''Cooling System''
| liquid cooling
| natural cooling
| liquid cooling
| forced air with speed control
| internal liquid cooling and heating system 
|
|}
|}



Revision as of 18:45, 30 October 2023

Yotta
Products SolarLeaf REV
Industry Residential Commercial, Industrial
Energy Capacity 1 kWh 500 kWh
Power Capacity 0.675 kW 24 kW
Storage Murata Murata
Inverter Yotta Yotta
Controller Yotta Yotta

Founded in 2017, Yotta is a designer and developer of integrated solar plus storage solutions for commercial and industrial markets. Originally a microinverter company, their product line has expanded to include LFP energy storage systems, the SolarLEAF; DC-coupled inverters, the dual-power inverter; asset management and reporting software, Yotta Vision; and prefabricated electric vehicle charging structures supported by solar and storage for on- or off-grid contexts and applications, the REV.

History

Yotta Energy was one of seven Caltech Rocket Fund Award recipients in 2020. Yotta also recently received demonstration funding via the CEC BRIDGE awards, focused on building rapid innovation and development to green energy technology.

Deployments

EPRI will be partnering closely with Yotta on this project to deploy, measure, assess, and evaluate the performance and efficacy of their rooftop solar plus storage solution at a multifamily apartment complex in Southern California.

Products

SolarLEAF

Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy. Though this increases the length of cable needed for wiring up an installation, each individual battery module can be easily carried, since the overall weight is spread out over a large number of units. The SolarLEAF is designed with passive thermal regulation technology that allows the systems to withstand being installed on top of hot roofs.

REV

The REV is a deployable EV charging system equipped with solar panels, battery energy storage, power inverters, and EV charging ports. It is meant to provide an off-grid EV charging solution to locations that cannot be serviced by grid-tied power. The battery energy capacity of the system is configurable from 50 to 300 kWh and its EV charging power capacity tops out at 24 kW. The REV is can be connected to the grid, but is also able to run off-grid, with its solar PV system, expandable from 15 to 50 kW.

Products SolarLEAF (SL-1000) REV
Industry Residential, Commercial Commercial, Industrial
Energy Capacity 14 kWh 14 kWh
Power Capacity 5 kW 770 kW
Storage various various
Inverter Tesla Tesla
Controller Tesla Tesla

Applications

SolarLEAF REV
Self-consumption yes yes
Backup Power yes yes
Energy Time Shift TOU yes
Peak Shaving yes yes
Demand Response yes
Demand Charge Reduction yes
Solar PV Charging yes yes
Solar (renewable) ramp limiting yes yes
Power Quality yes
Market participation
Spinning Reserves
Voltage Regulation
Frequency Regulation
Black Start
Resource Adequacy Capacity

Storage System

Yotta is reported to source its lithium iron phosphate batteries from Murata and their Fortelion line of energy storage cells.

Hybrid E5 Battery Energy Storage Cabinet
Technology Type Lithium ion Lithium ion
Storage Media Provider Panasonic Samsung SDI
Storage Media Model BX 6.0 224S1P
Coupling Type AC AC
Charge Capacity 750 Ah
Total Energy 6 kWh 41 kWh
Usable Energy 4.8 kWh
Rated Continuous Discharge Real Power 3.6 kW 129 kW
Max Peak Discharging Real Power 148 kW
Rated Continuous Charge Real Power 2.5 kW 122 kW
Max Peak Charging Real Power
Idle Load
Response time
DC Voltage (Nominal, Converter Output) 95 V 900 V
DC Voltage (Range) 85 to 104 V 716 V to 918 V
DC Voltage (Internal Battery) 51.8 V
Rated Continuous Discharge Current 35 A 143 A
Max Peak Discharging Current 200 A
Rated Continuous Charge Current 30 A 135 A
Max Peak Charging Current
Roundtrip Efficiency (AC) 97.8% (peak)

97.5% (CEC)

Roundtrip Efficiency (DC)
Degradation / Life (cycles) > 4000 cycles
Depth of Discharge 0.8 0.9
Modularity yes, via additional battery modules
Test conditions 15 DBS48V50S modules
Cooling System

Power Conversion System Specifications

The Yotta dual power mircoinverter (DPI) is installed alongside and connected to the SolarLEAF and also mounted underneath solar PV panels. The inverter is three-phase and can accept four inputs of solar PV panels or SolarLEAF. It is available in two different output voltage levels, the DPI-208 for 208 volts and the DPI-480 for 480 volts.

Hybrid E5 Battery Energy Storage Cabinet
Inverter Make Delta Delta
Inverter Model E5 Power Conditioning System
Rated AC Continuous Output Real Power 5 kW 125 kW
Max AC Peak Output Real Power
Idle Load 30 W < 20 W
Rated AC Continuous Output Apparent Power 5 kVA 125 kVA
Max AC Peak Output Apparent Power
Rated Reactive Power
Rated Continuous Output Current 150.4 A (linear load), 120 A (non-linear)
Max Peak Output Current 167 A
Rated Continuous Battery Input Power 122 kW
Max Peak Battery Input Power
Maximum Battery Input Current 163 A
Maximum Output Fault Current
Overcurrent Protection Device
Maximum Supply Fault Current
Power Factor Output Range 0.8 leading to 0.8 lagging adjust from -1 to 1
Power Factor Range (full-rated power)
Imbalance for Split-Phase Loads
Total Harmonic Distortion (THD) < 3% at rated power < 5% at rated power
Roundtrip Efficiency 0.972 97.8% (peak)

97.5% (CEC)

AC Connection Type single-phase three-phase, three-wire or four-wire
Nominal Output AC Voltage 230 V 480 V
Nominal Frequency 60 Hz 60 Hz
Packaging IP 65
Modularity
Cooling System natural cooling forced air with speed control

Energy Management System Specifications

Yotta's energy management system is Yotta Vision that provides users with data analytics and visibility into their system.

Powerwall 2 Powerwall+ Powerpack 2.0 Megapack
Energy Management System Tesla Tesla Tesla Tesla
Control Capabilities Backup power, solar PV self-consumption, time-based control, off-grid capability (coming soon) Backup power, solar PV self-consumption, time-based control, off-grid capability Peak shaving, load shifting, emergency backup, demand response, renewable integration, capacity reserve, ancillary services, T&D support
Portal availability Monitoring and control functions available on web / mobile device Tesla app Monitoring and control functions available on web / mobile device Tesla app
Communications & Network Ethernet, WiFi Ethernet, Wi-Fi, cellular LTE 4G Modbus TCP/IP; DNP3

Environment and Mechanical

Hybrid E5 Battery Energy Storage Cabinet
Energy Management System Delta Gridscape
Control Capabilities solar charging, backup power, maximum power point tracking
Portal availability LCD display User interface: 4.9in LCD screen w/ operation button & fault LED's

Emergency Stop: local button and remote control

Communications & Network RS-485 Ethernet, RS-485/Modbus RTU and CAN

Environment and Mechanical

Hybrid E5 Battery Energy Storage Cabinet
Mounting Wall Floor
Weight 75 kg (battery), 27 kg (inverter) 550 kg (battery)

305 kg (inverter)

Footprint 552 mm x 596 mm x 200 mm (battery), 510 mm x 445 mm x 177 mm (inverter) 600 mm x 660 mm x 2000 mm (battery)

600 mm x 800 mm x 1734 mm (inverter)

Indoor/outdoor Indoor / Outdoor Outdoor
Enclosure IP 55 (battery), IP 65 (inverter) NEMA 3R
Ingress Rating IP 55 (battery), IP 65 (inverter) IP 54
Noise < 72 db A @ 1 m
Operating temperature -10 °C to 45 °C (battery), -25 °C to 60 °C (inverter) -25 °C to 50 °C
Optimum temperature
Operating humidity 0% to 90 % noncondensing (battery), 0 % to 100 % (inverter) < 95% relative humidity, non-condensing
Altitude < 3000 m
Modularity

Warranty

Hybrid E5 Battery Energy Storage Cabinet
System Warranty
Battery Warranty
Inverter Warranty

Codes, Standards, and Regulations

Hybrid E5 Battery Energy Storage Cabinet
CPUC Rule 21 pending
FCC CFR Part 15 Class A pending
HECO Rule 14 yes
IEC 60950 yes
IEC 61000-6-2 yes
IEC 62040-1 yes
IEC 62109-1 yes
IEC 62116 yes
IEEE 1547 compliant, pending
UL 1741 pending
UL 1741SA pending
UL 1973 yes
UN 38.3 yes yes