Yotta

From EPRI Storage Wiki
Jump to navigation Jump to search
Yotta
Products SolarLeaf REV
Industry Commercial Commercial, Industrial
Energy Capacity 1 kWh 500 kWh
Power Capacity 0.675 kW 24 kW
Storage Murata Murata
Inverter Yotta Yotta
Controller Yotta Yotta

Founded in 2017, Yotta is a designer and developer of integrated solar plus storage solutions for commercial and industrial markets. Originally a microinverter company, their product line has expanded to include LFP energy storage systems, the SolarLEAF; DC-coupled inverters, the dual-power inverter; asset management and reporting software, Yotta Vision; and prefabricated electric vehicle charging structures supported by solar and storage for on- or off-grid contexts and applications, the REV.

History

Yotta Energy was one of seven Caltech Rocket Fund Award recipients in 2020. Yotta also recently received demonstration funding via the CEC BRIDGE awards, focused on building rapid innovation and development to green energy technology.

Deployments

EPRI will be partnering closely with Yotta on this project to deploy, measure, assess, and evaluate the performance and efficacy of their rooftop solar plus storage solution at a multifamily apartment complex in Southern California.

Products

SolarLEAF

Yotta's energy storage solution the SolarLEAF (SL-1000) is a lithium iron phosphate battery, mounted on the reverse or side of rooftop PV panels, hence the naming. This approach requires the deployment of many SolarLEAF modules in order for an installation to be of sizeable substance and efficacy. Though this increases the length of cable needed for wiring up an installation, each individual battery module can be easily carried, since the overall weight is spread out over a large number of units. The SolarLEAF is designed with passive thermal regulation technology that allows the systems to withstand being installed on top of hot roofs.

REV

The REV is a deployable EV charging system equipped with solar panels, battery energy storage, power inverters, and EV charging ports. It is meant to provide an off-grid EV charging solution to locations that cannot be serviced by grid-tied power. The battery energy capacity of the system is configurable from 50 to 300 kWh and its EV charging power capacity tops out at 24 kW. The REV is can be connected to the grid, but is also able to run off-grid, with its solar PV system, expandable from 15 to 50 kW.

Products SolarLEAF (SL-1000) REV
Industry Commercial Commercial, Industrial
Energy Capacity 1 kWh 500 kWh
Power Capacity 0.675 kW 24 kW
Storage Murata Murata
Inverter Yotta Yotta
Controller Yotta Yotta

Applications

SolarLEAF REV
Self-consumption yes yes
Backup Power yes yes
Energy Time Shift TOU yes
Peak Shaving yes yes
Demand Response yes
Demand Charge Reduction yes
Solar PV Charging yes yes
Solar (renewable) ramp limiting yes yes
Power Quality yes
Market participation
Spinning Reserves
Voltage Regulation
Frequency Regulation
Black Start
Resource Adequacy Capacity

Storage System

Yotta is reported to source its lithium iron phosphate batteries from Murata and their Fortelion line of energy storage cells.

SolarLEAF REV
Technology Type Lithium ion phosphate Lithium ion phosphate
Storage Media Provider Murata Murata
Storage Media Model Fortelion Fortelion
Coupling Type AC AC
Charge Capacity 26.4 Ah 750 Ah
Total Energy 1 kWh 600 kWh
Usable Energy 1 kWh 600 kWh
Rated Continuous Discharge Real Power 0.675 kW 48 kW
Max Peak Discharging Real Power 60 kW
Rated Continuous Charge Real Power 0.675 kW 34 kW
Max Peak Charging Real Power
Idle Load
Response time
DC Voltage (Nominal, Converter Output) 38.4 V
DC Voltage (Range) 22 to 45 V
DC Voltage (Internal Battery)
Rated Continuous Discharge Current 15 A
Max Peak Discharging Current 15 A
Rated Continuous Charge Current 135 A
Max Peak Charging Current
Roundtrip Efficiency (AC) 97.8% (peak)

97.5% (CEC)

Roundtrip Efficiency (DC)
Degradation / Life (cycles) > 8000 cycles (80% DoD)
Depth of Discharge 0.8 0.8
Modularity yes, via additional battery modules yes, via additional battery + PV modules
Test conditions
Cooling System

Power Conversion System Specifications

The Yotta dual power mircoinverter (DPI) is installed alongside and connected to the SolarLEAF and also mounted underneath solar PV panels. The inverter is three-phase and can accept four inputs of solar PV panels or SolarLEAF. It is available in two different output voltage levels, the DPI-208 for 208 volts and the DPI-480 for 480 volts.

DPI-208 DPI-480
Inverter Make Yotta Yotta
Inverter Model DPI-208 DPI-480
Rated AC Continuous Output Real Power 5 kW 125 kW
Max AC Peak Output Real Power
Idle Load 30 W < 20 W
Rated AC Continuous Output Apparent Power 5 kVA 125 kVA
Max AC Peak Output Apparent Power
Rated Reactive Power
Rated Continuous Output Current 150.4 A (linear load), 120 A (non-linear)
Max Peak Output Current 167 A
Rated Continuous Battery Input Power 122 kW
Max Peak Battery Input Power
Maximum Battery Input Current 163 A
Maximum Output Fault Current
Overcurrent Protection Device
Maximum Supply Fault Current
Power Factor Output Range 0.8 leading to 0.8 lagging adjust from -1 to 1
Power Factor Range (full-rated power)
Imbalance for Split-Phase Loads
Total Harmonic Distortion (THD) < 3% at rated power < 5% at rated power
Roundtrip Efficiency
AC Connection Type three-phase three-phase
Nominal Output AC Voltage 230 V 480 V
Nominal Frequency 60 Hz 60 Hz
Packaging
Modularity
Cooling System natural cooling forced air with speed control

Energy Management System Specifications

Yotta's energy management system is Yotta Vision that provides users with data analytics and visibility into their system.

Vision
Energy Management System Vision
Control Capabilities solar charging, backup power, maximum power point tracking
Portal availability
Communications & Network

Environment and Mechanical

SolarLEAF REV
Mounting Roof Floor
Weight 56.7 lb
Footprint 15.75 in x 26.25 in x 4.25 in (battery) 4.0 ft x 8.1 ft x 8.7 ft
Indoor/outdoor Outdoor Outdoor
Enclosure NEMA 67 / IP 67
Ingress Rating
Noise
Operating temperature -20° to 43 °C / -4° to 109 °F
Optimum temperature
Operating humidity 0% to 90 % noncondensing (battery), 0 % to 100 % (inverter) < 95% relative humidity, non-condensing
Altitude
Modularity by design, requires multiple SolarLEAFs expandable PV and storage sizes

Warranty

SolarLEAF REV
System Warranty 10 years 10 years
Battery Warranty 10 years 10 years
Inverter Warranty 10 years 10 years

Codes, Standards, and Regulations

Hybrid E5 Battery Energy Storage Cabinet
CPUC Rule 21 pending
FCC CFR Part 15 Class A pending
HECO Rule 14 yes
IEC 60950 yes
IEC 61000-6-2 yes
IEC 62040-1 yes
IEC 62109-1 yes
IEC 62116 yes
IEEE 1547 compliant, pending
UL 1741 pending
UL 1741SA pending
UL 1973 yes
UN 38.3 yes yes