Failure Event - France, Ariege, Perles-et-Castelet - 1 Dec 2020
Jump to navigation
Jump to search
Overview
Event Details | |
---|---|
Location: | France, Ariege, Perles-et-Castelet |
Capacity (MW): | 0.5 |
Capacity (MWh): | 0.5 |
Battery Module: | Narada [LFP] |
Integrator: | |
Application: | Hybrid Supercacitor plus Storage System |
Installation: | Substation |
Enclosure Type: | Container |
Event Date: | 1 December 2020 |
System Age (yr): | 0 |
Extent of Damage: | Fire |
State During Accident: | Commissioning, testing |
Description: | The substation has 500 kWh of batteries and 1 MW - 10s of supercapacitors. The supercapacitors were not involved in the cause of failure, which happened during acceptance testing. The investigation found that rack #2 suddenly discharged into rack #3, and the current passed through only modules #1 to #7 of rack #3. The insulation resistance of rack #2 fell below the safety threshold and neared short circuit for rack #3. The investigation report provides a hypothesis of two faults resulting in failure: an electrical connection failed and came into contact with the metal frame, and an insulation fault between the busbar connecting a module to the BPU box, which may have caused an electric arc upstream of the fuse. The container was destroyed. |
Source: | Investigation Report (English Translation) |
Additional Resources: | Investigation Report (Original source, French) |
- Note: Missing values in this table reflect unknowns.
If you have any details or corrections you would like to contribute to the database please reach out to our Storage Safety email.