This is a public resource for documenting publicly-available data on battery energy storage failure events from around the world. All information included is available in the linked public documents. If there is a public event that is not included in the BESS Fire Event Database, please email the relevant information and link to supporting info to Dirk Long.
If you would like to be notified when a new event is added to this database or are interested in other EPRI energy storage safety research resources and opportunities please reach out to Dirk Long.
Stationary Energy Storage Failure Events
This table tracks utility and C&I scale energy storage failure events with publicly available information.
- Note: Missing values in this table reflect unknowns.
| Location | Capacity (MWh) | Capacity (MW) | Application | Installation | Event Date | System Age (yr) | State During Accident | Source |
|---|
| UK, Rainworth | | 7 | Frequency regulation and grid support services | Rural | 1 May 2026 | 9 | | BBC |
| US, CA, San Marcos | | | EV charging | Parking lot | 21 January 2026 | | | San Diego Union-Tribune |
| US, NY, Warwick | 17.9 | 4 | Peak shaving | | 19 December 2025 | | | Village of Warwick |
| US, AZ, Peoria | 100 | 25 | Peak shaving | Substation | 1 October 2025 | 4 | Operational | AZ Family |
| US, NV, Boulder City | 360 | 90 | Solar shifting | Solar + storage | 23 September 2025 | 3.8 | | KTNV |
| US, CA, Parkfield | 240 | 60 | Solar integration | Solar + storage | 30 August 2025 | 4 | | Monterey County Sheriff's Office |
| Netherlands, Almelo | | | | Commercial | 4 August 2025 | | | 112 Nieuws |
| South Korea, Gyeongsangbuk-do, Songdong-ri | | | Industrial | Indoor | 16 June 2025 | | | News1 |
| South Korea, Gyeongsangbuk-do, Pohang City | | | Industrial | Building | 16 June 2025 | | Operational | Yonhap News Agency |
| US, OR, Hillsboro | | | Data center | Data center | 22 May 2025 | | | Fox 12 |
| England, Gloucestershire, Cirencester | 51 | 10 | Solar shifting | Solar + storage | 28 March 2025 | 2.5 | | Warrington Guardian |
| England, Essex, Tilbury | 600 | 300 | Frequency Regulation, Capacity Market, Balancing Mechanism, Wholesale Power Markets | Substation | 19 February 2025 | 0 | Construction | Energy Storage News |
| US, CA, Moss Landing | 1,200 | 300 | Resource Adequacy | Power Plant | 16 January 2025 | 4.1 | | EPA Presentation: Moss Landing Battery Fire Response |
| Spain, Valencia, Port of Gandia | | 1 | Port | Solar + storage | 5 January 2025 | | Operational | PV Magazine |
| South Africa, Table Mountain | | | Backup energy resource | Indoor | 25 October 2024 | | | Green Building Africa |
| Canada, ON, Brantford | | | Peak Shaving | Commercial | 12 September 2024 | 3 | | CTV News |
| Singapore | | | UPS | Data center | 10 September 2024 | | | DCD |
| US, CA, Escondido | 120 | 30 | | Substation | 5 September 2024 | 7.6 | Under maintenance | San Diego Union Tribune |
| US, CA, Santa Ana | | | Industrial | | 17 July 2024 | | | OC Register |
| USA, CA, San Diego | 250 | 250 | Energy shifting | | 15 May 2024 | 3.7 | | The San Diego Union-Tribune |
| US, CA, Kearny Mesa | 80 | 20 | | Substation | 29 April 2024 | 2.1 | | CPUC Draft Resolution ESRB-13 |
| Japan, Kagoshima, Isa | | | Solar Integration | | 27 March 2024 | | | FNN |
| Taiwan, Lanyu | | 1.1 | | Power Plant | 28 December 2023 | | Operational | United Daily News |
| USA, ID, Melba | 8 | 2 | Distribution Resource | Substation | 2 October 2023 | 0 | Pre-commissioning | KTVB7 |
| France, Martinique, Saint-Esprit | | | Solar Integration | Farm | 29 September 2023 | | Operational | DayFR Euro |
| Australia, Queensland, Bouldercombe | 100 | 50 | | Substation | 26 September 2023 | 0.1 | Operational | ABC News |
| US, CA, Valley Center | 560 | 140 | | Rural | 18 September 2023 | 1.6 | Operational | Valley Road Runner |
| France, Saucats, Barban | 98 | 105 | | Rural | 22 August 2023 | 0 | Pre-commissioning | dayFREuro |
| China, Xiangzhou District, Zuhai City | | | | Warehouse | 19 August 2023 | | | OFweek |
| US, NY, Chaumont | 15 | 5 | Solar Integration | Rural | 27 July 2023 | 0.4 | Operational | 7 News WWNYTV |
| Taiwan, Taichung City, Longjing District | | | | | 4 July 2023 | | | United Daily News |
| US, NY, Warwick | 17.9 | 4 | Energy Shifting, Backup | Substation | 27 June 2023 | 0.1 | Operational | Convergent Energy and Power |
| US, NY, Warwick | 36 | 8 | Energy Shifting, Backup | Substation | 26 June 2023 | 0.1 | Operational | Convergent Energy and Power |
| US, NY, East Hampton | 40 | 5 | Resiliency, Utility Peak Reduction | Substation | 31 May 2023 | 4.8 | Operational | East Hampton Star |
| Sweden, Gothenburg, Vastra Frolunda | 0.9 | | | Indoor | 26 April 2023 | 0 | Pre-commissioning | Battery Energy Storage Container Fire Report (English translation) |
| France, Corsica, Aghione | | 4 | Solar integration | Solar + storage | 6 April 2023 | | Operational | Fire and Rescue service of Haute Corse |
| France, Saint-Trivier-sur-Moignans | | | | Indoor, Datacenter | 28 March 2023 | | | DCD |
| US, PA, Millvale | | | Solar Integration | Urban | 30 January 2023 | | Operational | WTAE |
| South Korea, Jeollanam-do, Yeongam-gun, Geumjeong-myeon | 251 | | Solar Integration | Rural | 27 December 2022 | 1.8 | Operational | E2News.com |
| South Korea, Jeollanam-do, Damyang-gun, Mujeong-myeon, Deokgok-ri | 9.1 | 2.5 | Solar Integration | Rural | 8 December 2022 | 5.5 | Operational | E2News.com |
| China, Hainan | 50 | 25 | Solar Integration | | 20 October 2022 | 0 | Commissioning | china5e.com |
| South Korea, Pangyo | | | | Datacenter | 15 October 2022 | | | DCD |
| US, CA, Moss Landing | 730 | 182.5 | Energy Shifting, Ancillary Services | Substation | 20 September 2022 | 0.5 | Operational | KSBW News |
| South Korea, Incheon | | 103 | Energy Shifting | Factory | 6 September 2022 | | Operational | Teller Report |
| USA, Wyoming, Yellowstone National Park | | | Solar Integration | Indoor | 6 September 2022 | | | National Park Service |
| US, CA, Rio Dell | | | Solar Integration / Backup | Rural | 3 August 2022 | 4 | Operational | KRCR |
| France, Corsica, Poggio-di-Nazza | 4 | 4 | Solar integration | Solar + storage | 3 June 2022 | 1.8 | Operational | BEA-RI investigation report |
| South Korea, Jangseong-gun | | | Solar Integration | | 2 May 2022 | | | Newspim |
| US, AZ, Chandler | 40 | 10 | | Substation | 18 April 2022 | 3 | Operational | AZ Central |
| US, CA, Valley Center | 560 | 140 | | Rural | 5 April 2022 | 0.2 | Operational | Valley Road Runner |
Figure 1. A breakdown of the stationary energy storage failure events from the above table.
Other Energy Storage Failure Events
This table tracks other energy storage failure events for scenarios that do not fit the criteria of the table above. This could include energy storage failures in settings like electric transportation, recycling, manufacturing, etc.
- Note: Missing values in this table reflect unknowns.
| Location | Setting | Capacity (MWh) | Capacity (MW) | Operator / Integrator | Event Date | System Age (yr) | State During Accident | Source |
|---|
| Ireland, Claregalway | Battery manufacturer | | | Xerotech | 29 January 2025 | | Stored in container | Connacht Tribune |
| US, MO, Fredericktown | Battery recycling plant | | | Critical Mineral Recovery | 30 October 2024 | | | Missouri Independent |
| US, CA, San Pedro | On road during transport | | | | 26 September 2024 | | In transit | LB Post |
| Canada, Montreal | Temporary storage at a port | | | | 23 September 2024 | | | CTV News |
| US, NV, Nye County | On highway during transport | | | | 17 September 2024 | | In tranit | Review Journal |
| Germany, Thuringia | Temporary storage | | | Suncycle | 11 August 2024 | | Temporarily stored onsite; not interconnected | PV Magazine |
| US, South Carolina, Seneca | Manufacturing | | | BorgWarner | 8 August 2024 | | Battery on assembly line | WSPA |
| US, CA, Baker | On highway during transport | | | | 26 July 2024 | | In transit | CBS |
| Germany, Thuringia | | | | Suncycle | 30 June 2024 | | | MDR.DE |
| South Korea, Hwaseong | Manufacturing | | | Aricell | 24 June 2024 | | | New York Times |
| Germany, Thuringia | | | | Suncycle | 7 June 2024 | | | PV Magazine |
| Germany, Neermoor | Temporary storage | | | Intilion | 27 April 2024 | | Temporarily stored onsite; not interconnected | Neermoor Fire Brigade |
| US, Ohio, Columbus | | | | | 18 April 2024 | | | Firehouse |
| Scotland, Kilwinning | Recycling | | | | 8 April 2024 | | | BBC |
| Australia, Maryborough | On highway during transport | | | | 22 March 2024 | | In transit | ABC News |
| France, Viviez | Recycling | | | SNAM | 17 February 2024 | | Storage | Reuters |
| US, AK, Dutch Harbor | Maritime | | | | 29 December 2023 | | In transit | AP News |
| Germany, Wurzburg | Underground Parking Garage | | | | 5 November 2023 | | | Fireworld |
| Netherlands, Ameland | Maritime | | | Multiple | 26 July 2023 | | Storage | AP |
| France, Rouen | Warehouse | | | | 16 January 2023 | | Storage | the deep dive |
| US, CA, Baker | Electric Vehicle Charging Station | | | Tesla | 1 January 2023 | | Operational | Electrek |
| Germany, Kaufbeuren | Battery test laboratory | | | | 3 November 2022 | | Testing | Allgau Newspaper |
| US, CA, Palo Alto | EV Dealership | | | Tesla | 7 August 2022 | | Storage | Palo Alto Fire Dept. |
| Netherlands, Amsterdam | Maritime | 0.7 | | EST-Floattech | 25 July 2022 | 1 | In transit / operation | The Maritime Executive |
| US, WI, Milwaukee | Hospital parking garage | | | | 21 June 2022 | | recycling bin | WISN |
| Sweden, Karlskoga | Warehouse | | | | 10 April 2022 | | | SVT Nyheter |
| South Korea, North Chungcheong, Cheongju | Manufacturing | | | EcoPro BM | 21 January 2022 | | Operational Manufacturing Facility | Korea JoongAng Daily |
| China, Wuhan | On highway during transport | | | | 12 January 2022 | | during transportation | Jimu News |
| US, IL, Morris | Warehouse | | | Superior Battery Inc. | 2 July 2021 | | | ABC |
| US, NM, Albuquerque | Recycling | | | Friedman Recycling | 16 March 2021 | | | KOB |
| Norway, Oslo Fjord | Maritime | 0.8 | | Corvus Energy | 11 March 2021 | 2 | | Corvus Energy |
| China, Yunnan, Qujing | Manufacturing | | | CATL | 27 January 2021 | | | ESP |
| China, Hunan | Recycling | | | CATL, Brunp Recycling | 7 January 2021 | | | ESP |
| Norway, Sydnes | Maritime | 2 | | Corvus Energy | 10 October 2019 | 0.5 | | CFPA Europe |
| US, OR, Powin | New product testing | | | Powin HQ | 11 April 2019 | | | The Oregonian |