Location | Energy (MWh) | Power (MW) | Module Type | Application | Installation | Event Date | System Age (yr) | State During Accident | Source |
---|
USA, CA, San Diego | | 250 | LG Chem | Energy shifting | | 15 May 2024 | 3.7 | | The San Diego Union-Tribune |
Japan, Kagoshima, Isa | | | | Solar Integration | | 27 March 2024 | | | FNN |
Taiwan, Lanyu | | 1.1 | | | Power Plant | 28 December 2023 | | Operational | United Daily News |
USA, ID, Melba | 8 | 2 | Powin Energy | Distribution Resource | Substation | 2 October 2023 | 0 | Pre-commissioning | KTVB7 |
France, Martinique, Saint-Esprit | | | | Solar Integration | Farm | 29 September 2023 | | Operational | DayFR Euro |
Australia, Queensland, Bouldercombe | 100 | 50 | Tesla | | Substation | 26 September 2023 | 0.1 | Operational | ABC News |
US, CA, Valley Center | 560 | 140 | LG Energy Solution | | Rural | 18 September 2023 | 1.6 | Operational | Valley Road Runner |
France, Saucats, Barban | 98 | 105 | | | Rural | 22 August 2023 | 0 | Pre-commissioning | dayFREuro |
China, Xiangzhou District, Zuhai City | | | | | Warehouse | 19 August 2023 | | | OFweek |
US, NY, Chaumont | 15 | 5 | General Electric | Solar Integration | Rural | 27 July 2023 | 0.4 | Operational | 7 News WWNYTV |
Taiwan, Taichung City, Longjing District | | | LFP | | | 4 July 2023 | | | United Daily News |
US, NY, Warwick | 17.9 | 4 | Powin Energy | Energy Shifting, Backup | Substation | 27 June 2023 | 0.1 | Operational | Convergent Energy and Power |
US, NY, Warwick | 36 | 8 | Powin Energy | Energy Shifting, Backup | Substation | 26 June 2023 | 0.1 | Operational | Convergent Energy and Power |
US, NY, East Hampton | 40 | 5 | LG Chem | Resiliency, Utility Peak Reduction | Substation | 31 May 2023 | 4.8 | Operational | East Hampton Star |
Sweden, Gothenburg, Vastra Frolunda | 0.9 | | | | Indoor | 26 April 2023 | 0 | Pre-commissioning | Battery Energy Storage Container Fire Report (English translation) |
France, Saint-Trivier-sur-Moignans | | | | | Indoor, Datacenter | 28 March 2023 | | | DCD |
US, PA, Millvale | | | SimpliPhi Power (LFP) | Solar Integration | Urban | 30 January 2023 | | Operational | WTAE |
South Korea, Jeollanam-do, Yeongam-gun, Geumjeong-myeon | 251 | | | Solar Integration | Rural | 27 December 2022 | 1.8 | Operational | E2News.com |
South Korea, Jeollanam-do, Damyang-gun, Mujeong-myeon, Deokgok-ri | 9.1 | 2.5 | Samsung SDI | Solar Integration | Rural | 8 December 2022 | 5.5 | Operational | E2News.com |
China, Hainan | 50 | 25 | Ruipu | Solar Integration | | 20 October 2022 | 0 | Commissioning | china5e.com |
South Korea, Pangyo | | | SK On | | Datacenter | 15 October 2022 | | | DCD |
US, CA, Moss Landing | 730 | 182.5 | Tesla | Energy Shifting, Ancillary Services | Substation | 20 September 2022 | 0.5 | Operational | KSBW News |
South Korea, Incheon | | 103 | | Energy Shifting | Factory | 6 September 2022 | | Operational | Teller Report |
USA, Wyoming, Yellowstone National Park | | | | Solar Integration | Indoor | 6 September 2022 | | | National Park Service |
US, CA, Rio Dell | | | Lead Acid | Solar Integration / Backup | Rural | 3 August 2022 | 4 | Operational | KRCR |
South Korea, Jangseong-gun | | | | Solar Integration | | 2 May 2022 | | | Newspim |
US, AZ, Chandler | 40 | 10 | LG Chem [NMC] | | Substation | 18 April 2022 | 3 | Operational | AZ Central |
US, CA, Valley Center | 560 | 140 | LG Energy Solution | | Rural | 5 April 2022 | 0.2 | Operational | Valley Road Runner |
Taiwan, Taichung City, Longjing District | 1 | 1 | | Solar Integration | Power Plant | 30 March 2022 | 2 | Operational | Economic Daily |
US, CA, Moss Landing | 400 | 100 | LG Energy Solution | Solar Integration | Power Plant | 13 February 2022 | 1 | Operational | KSBW News |
South Korea, Gunwi-gun, Gyeongsangbuk-do | 1.5 | 0.45 | LG Energy Solution | Solar integration | Rural | 17 January 2022 | 3 | Operation. Fully charged | E2News |
South Korea, Nam-gu, Ulsan | 50 | 10 | SK Innovation | Peak Load Reduction | Urban | 12 January 2022 | 2 | Operational | E2News |
US, CA, Moss Landing | 1,200 | 300 | LG Energy Solution | Solar Integration | Power Plant | 4 September 2021 | 0.8 | | Vistra |
Australia, Victoria, Geelong | 450 | 300 | Tesla | Grid Stability | Rural | 30 July 2021 | 0 | Construction, Commissioning | ABC News |
Australia, Victoria, Moorabool | 450 | 300 | Tesla [NMC] | Grid Stability | Rural | 30 July 2021 | 0 | Construction, Commissioning | Investigation Report |
US, IL, LaSalle | 36 | 36 | Sinexcel [LFP] | Solar and Wind Integration, Frequency Regulation | Rural | 19 July 2021 | 1.6 | | WSPY |
Germany, Neuhardenberg | 5 | 5 | [LFP] | Solar Integration and Frequency Regulation | Indoor/Hangar | 18 July 2021 | 5 | | RBB 24 (Translated) |
Boulouparis, New Caledonia, France | | | | Solar Integration | Rural | 13 July 2021 | | | FranceTVInfo.fr |
France, New Caledonia, Boulouparis | | | | Solar Integration | Rural | 13 July 2021 | | | La 1ere (Translated) |
US, MI, Standish | | | | Demand Charge Mgmt | Substation | 19 April 2021 | | | WSGW |
China, Beijing | 25 | | Gotion High-Tech [LFP] | Solar Integration | Commercial | 16 April 2021 | 2 | Construction, Commissioning | Investigation Report (English Translation) |
Australia, Bohle Plains | 8 | 4 | Tesla | VPP | | 7 April 2021 | 1.2 | Commissioning | Queensland Government |
South Korea, Hongseong | | | LG Energy Solution | Solar Integration | | 6 April 2021 | 3 | | Business Korea |
Gogyeong-myeon, Gyeongsangbuk-do, South Korea | 4 | | LG Energy Solution | Solar Integration | | 11 March 2021 | | | Newspim |
France, Ariege, Perles-et-Castelet | 0.5 | 0.5 | Narada [LFP] | Hybrid Supercacitor plus Storage System | Substation | 1 December 2020 | 0 | Commissioning, testing | Investigation Report (English Translation) |
UK, Liverpool | 10 | 20 | | Frequency Regulation | | 15 September 2020 | 1.5 | | Investigation Report |
South Korea, Haenam | | | | Solar Integration | Field | 27 May 2020 | 2.2 | | E2 News (Translated) |
Australia, Brisbane | | | | | | 17 March 2020 | 6.7 | | Brisbane Times |
South Korea, Gimhae | 2.2 | | | Solar Integration | | 27 October 2019 | 1.5 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
South Korea, Hadong | 1.3 | | | Solar Integration | Mountains | 21 October 2019 | 1.2 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
South Korea, Gunwi | 1.5 | | | Solar Integration | Mountains | 29 September 2019 | 1.8 | Discharging | Social construction of fire accidents in battery energy storage systems in Korea |
South Korea, Pyeongchang | 21 | | | Wind Integration | Mountains | 24 September 2019 | 2.7 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
France, Vitry-sur-Seine | | | | | Datacenter | 16 September 2019 | | Maintenance | Univers Freebox |
South Korea, Yesan | 1.5 | | | Solar Integration | Mountains | 30 August 2019 | 1.7 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
South Korea, North Jeolla, Jangsu | 1 | | | Solar Integration | Mountains | 26 May 2019 | 1 | Charged, discharging | MOTIE Investigation, June 2019 |
South Korea, North Gyeongsang, Chilgok | 3.7 | | | Solar Integration | Mountains | 4 May 2019 | 2.2 | Charged, inactive | MOTIE Investigation, June 2019 |
US, AZ, Surprise | 2 | 2 | LG Chem [NMC] | Volt Reg., PQ, Solar int. | Substation | 19 April 2019 | 2.1 | | APS Investigation Report |
US, OR, Tualatin | | | Powin Energy | Manufacturing/Testing | | 11 April 2019 | 0 | Testing | Oregon Live |
South Korea, Ulsan | 46.8 | | | Demand Charge Mgmt | Factory | 21 January 2019 | 0.6 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, North Jeolla, Jangsu | 2.5 | | | Solar Integration | Mountains | 15 January 2019 | 0.8 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Gyeongsangnam, Yangsan | 3.3 | | | Demand Charge Mgmt | Factory | 14 January 2019 | 0.8 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Jeolla, Wando | 5.2 | | | Solar Integration | Mountains | 14 January 2019 | 1.2 | Charging | MOTIE Investigation, June 2019 |
South Korea, Gangwon, Samcheok | 2.7 | | | Solar Integration | Mountains | 22 December 2018 | 1 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, North Chungcheong, Jecheon | 9.3 | | | Demand Charge Mgmt | Mountains | 17 December 2018 | 1 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Gyeongsang, Geochang | 1.3 | | | Solar Integration | Mountains | 21 November 2018 | 0.6 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, Gyeongsangbuk-do, Mungyeong | 4.2 | | | Solar Integration | Mountains | 21 November 2018 | 0.9 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, North Gyeongsang, Yeongju | 3.7 | | | Solar Integration | Mountains | 12 November 2018 | 0.8 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Chungcheong, Cheonan | 1.2 | | | Solar Integration | Mountains | 12 November 2018 | 0.9 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, Gyeonggi, Yongin | 17.7 | | | Frequency Regulation | Factory | 18 October 2018 | 2.6 | Maintenance | MOTIE Investigation, June 2019 |
South Korea, Jeju | 0.2 | | | Solar Integration | | 14 September 2018 | 4 | Charging | MOTIE Investigation, June 2019 |
South Korea, Chungcheongnam, Taean | 6 | | | Solar Integration | Waterfront | 7 September 2018 | 0 | Installation | MOTIE Investigation, June 2019 |
South Korea, Chungcheongbuk-do, Yeongdong | 6 | | | Solar Integration | Mountains | 1 September 2018 | 0.7 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, Sejong | 18 | | | Demand Charge Mgmt | Factory | 28 July 2018 | 0 | Installation | MOTIE Investigation, June 2019 |
South Korea, South Gyeongsang, Geochang | 9.7 | | | Wind Integration | Mountains | 21 July 2018 | 1.6 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Jeolla, Haenam | 3 | | | Solar Integration | Waterfront | 12 July 2018 | 0.6 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, North Jeolla, Gunsan | 19 | | | Solar Integration | Waterfront | 15 June 2018 | 0.5 | Charged, inactive | MOTIE Investigation, June 2019 |
South Korea, South Jeolla, Yeongam | 14 | | | Wind Integration | Mountains | 2 June 2018 | 2.4 | Maintenance | MOTIE Investigation, June 2019 |
South Korea, North Gyeongsang, Gyeongsan | 8.6 | | | Frequency Regulation | Mountains | 2 May 2018 | 1.8 | Maintenance | MOTIE Investigation, June 2019 |
China, Shanxi | | | | | | 21 December 2017 | | | Sohu |
Belgium, Drogenbos | | 6 | | Frequency Regulation | Research Park | 11 November 2017 | | | GTM |
South Korea, North Jeolla, Gochang | 1.5 | | | Wind Integration | Waterfront | 2 August 2017 | 0 | Installation | MOTIE Investigation, June 2019 |
China, Shanxi | | | | | | 7 March 2017 | | | Sohu |
US, WI, Franklin | | | | | Factory | 10 August 2016 | 0 | Assembly, Installation | S&C |
US, WA, Port Angeles | | | | Energy Shifting | Mall | 3 July 2013 | | | Peninsula Daily News |
US, AZ, Flagstaff | 1.5 | 0.5 | | Solar integration | | 26 November 2012 | 1.5 | | AZ Daily Sun |
US, HI, Kahuku | 10 | 15 | Xtreme [PbA] | Wind Integration | Island | 1 August 2012 | 1.5 | | Hawaii News Now |
Japan, Ibaraki Prefecture | | 2 | NGK [NaS] | | Industrial | 21 September 2011 | | | NGK |