| | =About EPRI's Battery Energy Storage System Failure Incident Database= |
| | The database compiles information about stationary battery energy storage system (BESS) failure incidents. There are two tables in this database: |
| | * Stationary Energy Storage Failure Incidents – this table tracks utility-scale and commercial and industrial (C&I) failures. |
| | * Other Storage Failure Incidents – this table tracks incidents that do not fit the criteria for the first table. This could include failures involving the manufacturing, transportation, storage, and recycling of energy storage. |
| | |
| | Residential energy storage system failures are not currently tracked. |
| | |
| | If you would like to be notified when a new event is added to this database or are interested in other EPRI energy storage safety research resources and opportunities please reach out to [mailto:Storage-Safety@epri.com Storage-Safety@epri.com]. For more information on energy storage safety, visit the [https://storagewiki.epri.com/index.php/Storage_Safety Storage Safety Wiki Page]. |
| | |
| | ==About the BESS Failure Incident Database== |
| | The BESS Failure Incident Database<ref>This database was formerly known as the BESS Failure Event Database. It has been renamed to the BESS Failure Incident Database to align with language used by the emergency response community. An ‘incident’ according to the Federal Emergency Management Agency (FEMA) is an occurrence, natural or man-made, that requires an emergency response to protect life or property, while an ‘event’ is a planned, non-emergency activity. The use of incident is prevalent, for example, in referring to the Incident Command, or Incident Command System used by public and private agencies to coordinate incident management operations. See |
| | https://www.fema.gov/pdf/emergency/nrf/nrf-glossary.pdf</ref> was initiated in 2021 as part of a wider suite of BESS safety research after the concentration of lithium ion BESS fires in South Korea and the Surprise, AZ, incident in the US. The database was created to inform energy storage industry stakeholders and the public on BESS failures. |
| | |
| | Tracking information about systems that have experienced an incident, including age, manufacturer, chemistry, and application, could inform R&D actions taken by the industry to improve storage safety. The focus of the database is on incidents that had a wider public health and safety impact, rather than on operational failures. Some helpful definitions follow: |
| | |
| | * BESS: A stationary energy storage system using battery technology. The focus of the database is on lithium ion technologies, but other battery technology failure incidents are included. |
| | * Failure incident: An occurrence caused by a BESS system or component failure which resulted in increased safety risk. For lithium ion BESS, this is typically a thermal risk such as fire or explosion. |
| | * Utility-scale: This refers to systems and projects that are interconnected to the grid. |
| | * C&I: This includes systems and projects that are behind-the-meter installations. Residential system failures are not currently tracked. Note that the Stationary Energy Storage Failure Incidents table tracks both utility-scale and C&I system failures. |
| | |
| | ==The Data in Context== |
| | |
| | [[File:Failure Rate Chart FINAL rev3b.png|900px]] |
| | |
| | |
| | |
| | It is instructive to compare the number of failure incidents over time against the deployment of BESS. The graph shows the failure rate per cumulative deployed capacity, up to 12/31/2025. This graph includes 33 non-public incidents that EPRI is aware of. These incidents are not included in the database itself, but they are reflected in the graph above. The global installed capacity of utility-scale BESS has dramatically increased over the last five years, and while failure incidents continue to occur, the overall rate of incidents has sharply decreased. The failure rate dropped by 99% from 2018 to 2025 as lessons learned from early failures have been incorporated into the latest designs and best practices. |
| | |
| | The battery industry continues to engage in R&D activities to improve risk reduction measures. |
| | |
| | ==Root Cause Categorization== |
| | The database includes the cause of failure for each incident, where available. EPRI, TWAICE, and the Pacific Northwest National Laboratory (PNNL) collaborated on an effort to classify the root cause of each incident in the database. The team used the best available information to categorize root cause (e.g., design; manufacturing; integration, assembly & construction; operation; or combination thereof) and the physical location of failure (e.g., cell/module, controls, balance-of-system equipment) to broadly classify the incidents for later comparison and contrast. These are based on technical details in the publicly available reporting, personal communications with entities involved and engineering judgement by industry experts. The published report [https://www.epri.com/research/products/000000003002030360 Insights from EPRI’s Battery Energy Storage Systems (BESS) Failure Incident Database: Analysis of Failure Root Cause] contains the methodology and results of this root cause analysis. |
| | |
| | ==Database Methodology== |
| | The information in this database is gathered from media reports and other public documents, such as released root cause analyses (RCA) or corporate press releases. Source documents are identified by active searching of global English-language media, and passive collection of reports through keyword flagging on internet websites and RSS feeds. Crowdsourced information that can be verified through publicly available documentation is also incorporated. |
| | |
| | All linked citations have been downloaded (or subsequently re-located on InternetArchive or WayBackMachine after removal), to preserve the available information from each incident. |
| | |
| | The database was begun in 2021, though it includes incidents as far back as 2011. EPRI engages in every effort to ensure that the information in the database is complete and accurate. Outside of online media, EPRI has used academic publications and collaborated with other organizations tracking failures to ensure all known incidents are captured. However, many incidents are not reported in news media, especially before 2018-19 when there was a renewed industry focus on safety. EPRI cannot guarantee that the database captures every relevant BESS failure incident, nor can we guarantee that all project data related to an incident is captured. If you are aware of missing data, please contact our [mailto:Storage-Safety@epri.com Storage-Safety@epri.com]. |
|
| |
|
| This is a public resource for documenting publicly-available data on battery energy storage failure events from around the world. All information included is available in the linked public documents. If there is a public event that is not included in the BESS Fire Event Database, please email the relevant information and link to supporting info to our [mailto:Storage-Safety@epri.com Storage Safety email].
| | Once an incident is identified, EPRI reaches out to involved parties for interviews whenever possible, and then links to formal reports released by any investigative entities once they are published. EPRI is also occasionally involved in RCAs or technical evaluations of incidents directly. For example, EPRI provided technical support for the investigation of the [https://storagewiki.epri.com/index.php/Failure_Event_-_UK,_Liverpool_-_15_Sep_2020 Carnegie Road, UK incident] in 2020, and published a [https://www.epri.com/research/products/000000003002026396 report] on the findings. |
|
| |
|
| If you would like to be notified when a new event is added to this database or are interested in other EPRI energy storage safety research resources and opportunities please reach out to our [mailto:Storage-Safety@epri.com Storage Safety email].
| | The included incidents are intended to reflect global activity. However, the database is necessarily limited to public reporting and may have missed incidents with minimal or local-only media coverage. Our automated alerts may not capture local language sources, which is why we engage in outreach and publicizing of the database. EPRI has reports from several recent incidents in Taiwan and South Korea that use local language sources and have paid to get translations where applicable. Substantial time has been spent to make sure incident information is accurate, and EPRI continues to corroborate incidents using other sources and update incidents (both new and old) regularly. |
|
| |
|
| =Stationary Energy Storage Failure Events= | | ==Database Citation== |
| This table tracks utility and C&I scale energy storage failure events with publicly available information. | | You are welcome and encouraged to use this database and cite it; the preferred format is below: |
| * [https://storagewiki.epri.com/resources/assets/BESS_Failure_Database/Failure_DB_List.csv Click here to download a csv version of the data in this table.] | | |
| | EPRI BESS Failure Incident Database. Accessed MM/DD/YYYY. https://storagewiki.epri.com/index.php/BESS_Failure_Incident_Database. |
| | |
| | If the database is the centerpiece of an analysis, we request that you reach out to EPRI at [mailto:Storage-Safety@epri.com Storage-Safety@epri.com] for review of the data application. We have a wealth of information on many [https://storagewiki.epri.com/index.php/Storage_Safety BESS safety topics] that can bolster your study and provide needed context. We are also tracking applications of the database to solicit continued EPRI support for maintenance. If you find this useful, please let us know! |
| | |
| | =Stationary Energy Storage Failure Incidents= |
| | This table tracks utility and C&I scale energy storage failure incidents with publicly available information. |
| | * [https://storagewiki.epri.com/resources/assets/BESS\_Failure\_Database/Failure\_DB\_List.csv Click here to download a csv version of the data in this table.] |
|
| |
|
| ''Note: Missing values in this table reflect unknowns.'' | | ''Note: Missing values in this table reflect unknowns.'' |
| Line 15: |
Line 63: |
| [[Category:Failure Event]] | | [[Category:Failure Event]] |
| [[Has Failure Event Category::ESS]] | | [[Has Failure Event Category::ESS]] |
| | [[Modification date::+]] |
| |mainlabel=- | | |mainlabel=- |
| |sort=Has Event Date | | |sort=Has Event Date |
| Line 42: |
Line 91: |
| </html> | | </html> |
|
| |
|
| =Other Energy Storage Failure Events= | | =Other Energy Storage Failure Incidents= |
| This table tracks other energy storage failure events for scenarios that do not fit the criteria of the table above. This could include energy storage failures in settings like electric transportation, recycling, manufacturing, etc. | | This table tracks other energy storage failure incidents for scenarios that do not fit the criteria of the table above. This could include energy storage failures in settings like electric transportation, recycling, manufacturing, etc. |
|
| |
|
| :''Note: Missing values in this table reflect unknowns.'' | | :''Note: Missing values in this table reflect unknowns.'' |
| Line 66: |
Line 115: |
| |headers=show | | |headers=show |
| }} | | }} |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-07-18 -->
| | |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-07-19 -->
| | ---- |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-07-19 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-08 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-15 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-15 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-15 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-15 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-08-15 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-09-20 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-09-20 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-09-20 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-04 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-04 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-06 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-18 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-18 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-24 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-24 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-24 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-30 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-30 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-31 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-31 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-31 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-31 -->
| |
| <!-- This is an automated comment to force the "last edited" timestamp to update. Feel free to delete these! - 2023-10-31 -->
| |
About EPRI's Battery Energy Storage System Failure Incident Database
The database compiles information about stationary battery energy storage system (BESS) failure incidents. There are two tables in this database:
- Stationary Energy Storage Failure Incidents – this table tracks utility-scale and commercial and industrial (C&I) failures.
- Other Storage Failure Incidents – this table tracks incidents that do not fit the criteria for the first table. This could include failures involving the manufacturing, transportation, storage, and recycling of energy storage.
Residential energy storage system failures are not currently tracked.
If you would like to be notified when a new event is added to this database or are interested in other EPRI energy storage safety research resources and opportunities please reach out to Storage-Safety@epri.com. For more information on energy storage safety, visit the Storage Safety Wiki Page.
About the BESS Failure Incident Database
The BESS Failure Incident Database[1] was initiated in 2021 as part of a wider suite of BESS safety research after the concentration of lithium ion BESS fires in South Korea and the Surprise, AZ, incident in the US. The database was created to inform energy storage industry stakeholders and the public on BESS failures.
Tracking information about systems that have experienced an incident, including age, manufacturer, chemistry, and application, could inform R&D actions taken by the industry to improve storage safety. The focus of the database is on incidents that had a wider public health and safety impact, rather than on operational failures. Some helpful definitions follow:
- BESS: A stationary energy storage system using battery technology. The focus of the database is on lithium ion technologies, but other battery technology failure incidents are included.
- Failure incident: An occurrence caused by a BESS system or component failure which resulted in increased safety risk. For lithium ion BESS, this is typically a thermal risk such as fire or explosion.
- Utility-scale: This refers to systems and projects that are interconnected to the grid.
- C&I: This includes systems and projects that are behind-the-meter installations. Residential system failures are not currently tracked. Note that the Stationary Energy Storage Failure Incidents table tracks both utility-scale and C&I system failures.
The Data in Context
It is instructive to compare the number of failure incidents over time against the deployment of BESS. The graph shows the failure rate per cumulative deployed capacity, up to 12/31/2025. This graph includes 33 non-public incidents that EPRI is aware of. These incidents are not included in the database itself, but they are reflected in the graph above. The global installed capacity of utility-scale BESS has dramatically increased over the last five years, and while failure incidents continue to occur, the overall rate of incidents has sharply decreased. The failure rate dropped by 99% from 2018 to 2025 as lessons learned from early failures have been incorporated into the latest designs and best practices.
The battery industry continues to engage in R&D activities to improve risk reduction measures.
Root Cause Categorization
The database includes the cause of failure for each incident, where available. EPRI, TWAICE, and the Pacific Northwest National Laboratory (PNNL) collaborated on an effort to classify the root cause of each incident in the database. The team used the best available information to categorize root cause (e.g., design; manufacturing; integration, assembly & construction; operation; or combination thereof) and the physical location of failure (e.g., cell/module, controls, balance-of-system equipment) to broadly classify the incidents for later comparison and contrast. These are based on technical details in the publicly available reporting, personal communications with entities involved and engineering judgement by industry experts. The published report Insights from EPRI’s Battery Energy Storage Systems (BESS) Failure Incident Database: Analysis of Failure Root Cause contains the methodology and results of this root cause analysis.
Database Methodology
The information in this database is gathered from media reports and other public documents, such as released root cause analyses (RCA) or corporate press releases. Source documents are identified by active searching of global English-language media, and passive collection of reports through keyword flagging on internet websites and RSS feeds. Crowdsourced information that can be verified through publicly available documentation is also incorporated.
All linked citations have been downloaded (or subsequently re-located on InternetArchive or WayBackMachine after removal), to preserve the available information from each incident.
The database was begun in 2021, though it includes incidents as far back as 2011. EPRI engages in every effort to ensure that the information in the database is complete and accurate. Outside of online media, EPRI has used academic publications and collaborated with other organizations tracking failures to ensure all known incidents are captured. However, many incidents are not reported in news media, especially before 2018-19 when there was a renewed industry focus on safety. EPRI cannot guarantee that the database captures every relevant BESS failure incident, nor can we guarantee that all project data related to an incident is captured. If you are aware of missing data, please contact our Storage-Safety@epri.com.
Once an incident is identified, EPRI reaches out to involved parties for interviews whenever possible, and then links to formal reports released by any investigative entities once they are published. EPRI is also occasionally involved in RCAs or technical evaluations of incidents directly. For example, EPRI provided technical support for the investigation of the Carnegie Road, UK incident in 2020, and published a report on the findings.
The included incidents are intended to reflect global activity. However, the database is necessarily limited to public reporting and may have missed incidents with minimal or local-only media coverage. Our automated alerts may not capture local language sources, which is why we engage in outreach and publicizing of the database. EPRI has reports from several recent incidents in Taiwan and South Korea that use local language sources and have paid to get translations where applicable. Substantial time has been spent to make sure incident information is accurate, and EPRI continues to corroborate incidents using other sources and update incidents (both new and old) regularly.
Database Citation
You are welcome and encouraged to use this database and cite it; the preferred format is below:
EPRI BESS Failure Incident Database. Accessed MM/DD/YYYY. https://storagewiki.epri.com/index.php/BESS_Failure_Incident_Database.
If the database is the centerpiece of an analysis, we request that you reach out to EPRI at Storage-Safety@epri.com for review of the data application. We have a wealth of information on many BESS safety topics that can bolster your study and provide needed context. We are also tracking applications of the database to solicit continued EPRI support for maintenance. If you find this useful, please let us know!
Stationary Energy Storage Failure Incidents
This table tracks utility and C&I scale energy storage failure incidents with publicly available information.
Note: Missing values in this table reflect unknowns.
| Location | Energy (MWh) | Power (MW) | Module Type | Application | Installation | Event Date | System Age (yr) | State During Accident | Source |
|---|
| UK, Rainworth | | 7 | NMC | Frequency regulation and grid support services | Rural | 1 May 2026 | 9 | | BBC |
| US, CA, San Marcos | | | Li ion | EV charging | Parking lot | 21 January 2026 | | | San Diego Union-Tribune |
| US, NY, Warwick | 17.9 | 4 | LFP | Peak shaving | | 19 December 2025 | | | Village of Warwick |
| US, AZ, Peoria | 100 | 25 | NMC | Peak shaving | Substation | 1 October 2025 | 4 | Operational | AZ Family |
| US, NV, Boulder City | 360 | 90 | NMC | Solar shifting | Solar + storage | 23 September 2025 | 3.8 | | KTNV |
| US, CA, Parkfield | 240 | 60 | NMC | Solar integration | Solar + storage | 30 August 2025 | 4 | | Monterey County Sheriff's Office |
| Netherlands, Almelo | 0.2 | | | | Commercial | 4 August 2025 | | | 112 Nieuws |
| South Korea, Gyeongsangbuk-do, Pohang City | 62.1 | | Li ion | Industrial | Building | 16 June 2025 | | Operational | Yonhap News Agency |
| South Korea, Angang‑eup, Gyeongju, North Gyeongsang Province | | 1.32 | LG Chem | Solar+storage | | 16 June 2025 | 8 | | News Tomato |
| South Korea, Angang-eup, Gyeongju, North Gyeongsang Province | | 1.32 | LG Chem | Solar+storage | | 16 June 2025 | 8 | | News Tomato |
| South Korea, Gi‑eun‑ri, Daesan‑eup, Seosan‑si, Chungcheongnam‑do | | | | Solar+storage | | 1 June 2025 | | | OhmyNews |
| South Korea, Gi-eun-ri, Daesan-eup, Seosan-si, Chungcheongnam-do | | | | Solar+storage | | 1 June 2025 | | | OhmyNews |
| US, OR, Hillsboro | | | | Data center | Data center | 22 May 2025 | | | Fox 12 |
| England, Gloucestershire, Cirencester | 51 | 10 | Li ion | Solar shifting | Solar + storage | 28 March 2025 | 2.5 | | Warrington Guardian |
| South Korea, Doam‑myeon, Gangjin‑gun, Jeollanam‑do, Seokmun‑ri | 35 | | | | | 9 March 2025 | | | Newsis |
| South Korea, Doam-myeon, Gangjin-gun, Jeollanam-do, Seokmun-ri | 35 | | | | | 9 March 2025 | | | Newsis |
| England, Essex, Tilbury | 600 | 300 | | Frequency Regulation, Capacity Market, Balancing Mechanism, Wholesale Power Markets | Substation | 19 February 2025 | 0 | Construction | Energy Storage News |
| South Korea, Bugui‑myeon, Jinan‑gun, North Jeolla (Jeonbuk) | | | | | | 19 January 2025 | | | News1 |
| South Korea, Bugui-myeon, Jinan-gun, North Jeolla (Jeonbuk) | | | | | | 19 January 2025 | | | News1 |
| US, CA, Moss Landing | 1,200 | 300 | LG Energy Solution | Resource Adequacy | Power Plant | 16 January 2025 | 4.1 | | EPA Presentation: Moss Landing Battery Fire Response |
| Spain, Valencia, Port of Gandia | 4 | 1 | Li ion | Port | Solar + storage | 5 January 2025 | 2 | Operational | PV Magazine |
| South Korea, Anjwa‑myeon (Anjwa Township), Shinan‑gun, Jeollanam‑do | 340 | 96 | LG Chem | Solar+storage | | 4 January 2025 | 3.9 | | FPN |
| South Korea, Anjwa-myeon (Anjwa Township), Shinan-gun, Jeollanam-do | 340 | 96 | LG Chem | Solar+storage | | 4 January 2025 | 3.9 | | FPN |
| Asia, 2025 Incident A | | | | | | 1 January 2025 | | | Confidential |
| China, 2025 Incident A | | | | | | 1 January 2025 | | | Confidential |
| China, 2025 Incident B | | | | | | 1 January 2025 | | | Confidential |
| China, 2025 Incident C | | | | | | 1 January 2025 | | | Confidential |
| China, 2025 Incident D | | | | | | 1 January 2025 | | | Confidential |
| UK, 2025 Incident A | | | | | | 1 January 2025 | | | Confidential |
| US, 2025 Incident A | | | | | | 1 January 2025 | | | Confidential |
| South Korea, Hongnong‑eup, Dandeok‑ri, Yeonggwang‑gun, Jeollanam‑do | | 1.6 | | Solar+storage | | 12 November 2024 | | | YG News |
| South Korea, Hongnong-eup, Dandeok-ri, Yeonggwang-gun, Jeollanam-do | | 1.6 | | Solar+storage | | 12 November 2024 | | | YG News |
| South Africa, Table Mountain | | | | Backup energy resource | Indoor | 25 October 2024 | | | Green Building Africa |
| South Korea, Soryong‑dong, Gunsan‑si, Jeonbuk | 102 | | | Peak shaving | | 10 October 2024 | | | YNA |
| South Korea, Soryong-dong, Gunsan-si, Jeonbuk | 102 | | | Peak shaving | | 10 October 2024 | | | YNA |
| Canada, ON, Brantford | | | | Peak Shaving | Commercial | 12 September 2024 | 3 | | CTV News |
| Singapore | | | | UPS | Data center | 10 September 2024 | | | DCD |
| US, CA, Escondido | 120 | 30 | Samsung SDI | | Substation | 5 September 2024 | 7.6 | Under maintenance | San Diego Union Tribune |
| Netherlands, Zuidland | 0.7 | | | | | 22 July 2024 | | | Rijnmond |
| US, CA, Santa Ana | 24 | 6 | | Industrial | | 17 July 2024 | 2.4 | | OC Register |
| South Korea, Baeksu‑eup, Yeonggwang‑gun, Jeollanam‑do | 312 | 100 | | Solar+storage | | 13 June 2024 | 3.5 | | Energy News |
| South Korea, Baeksu-eup, Yeonggwang-gun, Jeollanam-do | 312 | 100 | | Solar+storage | | 13 June 2024 | 3.5 | | Energy News |
| US, CA, Otay Mesa | 250 | 250 | LG Chem | Energy shifting | | 15 May 2024 | 3.7 | | The San Diego Union-Tribune |
| US, CA, Kearny Mesa | 80 | 20 | LFP | | Substation | 29 April 2024 | 2.1 | | CPUC Draft Resolution ESRB-13 |
| Germany, Priestewitz | 3.7 | | Intilion | | | 18 April 2024 | 1.1 | | Saechsische |
| Japan, Kagoshima, Isa | 3.5 | | | Solar Integration | | 27 March 2024 | | | FNN |
| US, CA, Mojave | 140 | 66 | LG | | Solar + storage | 22 February 2024 | 2.2 | | CA Spill Database |
| China, 2024 Incident A | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident B | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident C | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident D | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident E | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident F | | | | | | 1 January 2024 | | | Confidential |
| China, 2024 Incident G | | | | | | 1 January 2024 | | | Confidential |
| North America, 2024 Incident A | | | | | | 1 January 2024 | | | Confidential |
| US, 2024 Incident A | | | | | | 1 January 2024 | | | Confidential |
| US, 2024 Incident B | | | | | | 1 January 2024 | | | Confidential |
| US, 2024 Incident C | | | | | | 1 January 2024 | | | Confidential |
| US, 2024 Incident D | | | | | | 1 January 2024 | | | Confidential |
| Taiwan, Lanyu | | 1.1 | | | Power Plant | 28 December 2023 | | Operational | United Daily News |
| Belgium, Braives | | | | | | 26 December 2023 | | | Fire at the Proxy Delhaize in Braives: "Because of these electric batteries, my entire store almost went up in smoke..." (video) |
| Netherlands, Helmond | 9.3 | | | | Industrial park | 25 December 2023 | | | Nederlands Instituut Publieke Veiligheid |
| South Korea, Sinbuk‑myeon, Galgok‑ri, Yeongam‑gun, Jeollanam‑do | | | | Solar+storage | | 7 December 2023 | | | Newsis |
| South Korea, Sinbuk-myeon, Galgok-ri, Yeongam-gun, Jeollanam-do | | | | Solar+storage | | 7 December 2023 | | | Newsis |
| South Korea, Sigok-ri, Songhak-myeon, Jecheon-si, Chungcheongbuk-do | | | | Solar+storage | | 17 October 2023 | | | CC Daily News |
| US, ID, Melba | 8 | 2 | Powin Energy | Distribution Resource | Substation | 2 October 2023 | 0 | | KTVB7 |
| France, Martinique, Saint-Esprit | 1 | | | Solar Integration | Farm | 29 September 2023 | 2 | Operational | DayFR Euro |
| Australia, Queensland, Bouldercombe | 100 | 50 | Tesla | | Substation | 26 September 2023 | 0.1 | Operational | ABC News |
| South Korea, Shinchon‑dong, Seongsan‑gu, Changwon, Gyeongsangnam‑do | 175 | 35 | Samsung SDI | Peak shaving BESS only | | 25 September 2023 | 5 | | Electimes |
| South Korea, Shinchon-dong, Seongsan-gu, Changwon, Gyeongsangnam-do | 175 | 35 | Samsung SDI | Peak shaving BESS only | | 25 September 2023 | 5 | | Electimes |
| US, CA, Valley Center | 560 | 140 | LG Energy Solution | | Rural | 18 September 2023 | 1.6 | Operational | Valley Road Runner |
| South Korea, Onsan‑eup, Ulju‑gun, Ulsan | | 150 | | Peak shaving BESS only | | 23 August 2023 | 5.4 | | Yonhap News Agency |
| South Korea, Onsan-eup, Ulju-gun, Ulsan | | 150 | | Peak shaving BESS only | | 23 August 2023 | 5.4 | | Yonhap News Agency |
| France, Saucats, Barban | 98 | 105 | | | Rural | 22 August 2023 | 0 | Pre-commissioning | dayFREuro |
| China, Xiangzhou District, Zuhai City | 3.5 | | | | Warehouse | 19 August 2023 | | | OFweek |
| US, NY, Chaumont | 15 | 5 | General Electric | Solar Integration | Rural | 27 July 2023 | 0.4 | Operational | 7 News WWNYTV |
| Taiwan, Taichung City, Longjing District | | | LFP | | | 4 July 2023 | | | United Daily News |
| US, NY, Warwick | 22 | 4 | Powin Energy | Energy Shifting, Backup | Substation | 27 June 2023 | 0.1 | Operational | Convergent Energy and Power |
| US, NY, Warwick | 36 | 8 | Powin Energy | Energy Shifting, Backup | Substation | 26 June 2023 | 0.1 | Operational | Convergent Energy and Power |
| South Korea, Imok-ri, Hwayang-myeon, Yeosu-si | | | | | | 2 June 2023 | | | Namdo Today |
| US, NY, East Hampton | 40 | 5 | LG Chem | Resiliency, Utility Peak Reduction | Substation | 31 May 2023 | 4.8 | Operational | East Hampton Star |
| Sweden, Gothenburg, Vastra Frolunda | 0.9 | | | | Indoor | 26 April 2023 | 0 | Pre-commissioning | Battery Energy Storage Container Fire Report (English translation) |
| South Korea, Dongmyeon‑myeon, Chilgok‑gun | 9.1 | | | Solar+storage | | 7 April 2023 | | | Newspim |
| South Korea, Dongmyeon-myeon, Chilgok-gun | 9.1 | | | Solar+storage | | 7 April 2023 | | | Newspim |
| France, Corsica, Aghione | 3.5 | 4 | | Solar integration | Solar + storage | 6 April 2023 | | Operational | Fire and Rescue service of Haute Corse |
| France, Saint-Trivier-sur-Moignans | | | | | Indoor, Datacenter | 28 March 2023 | | | DCD |
| South Korea, Palgeum-myeon, Shinan-gun, South Jeolla Province | | | LG Energy Solution | | | 8 February 2023 | | | News1 |
| US, PA, Millvale | | | SimpliPhi Power (LFP) | Solar Integration | Urban | 30 January 2023 | | Operational | WTAE |
| South Korea, Hwangsan-myeon, Haenam-gun, Jeollanam-do | 11.7 | | | Solar+Storage | | 17 January 2023 | | | Gwangju MBC News |
| China, 2023 Incident A | | | | | | 1 January 2023 | | | Confidential |
| China, 2023 Incident B | | | | | | 1 January 2023 | | | Confidential |
| China, 2023 Incident C | | | | | | 1 January 2023 | | | Confidential |
| China, 2023 Incident D | | | | | | 1 January 2023 | | | Confidential |
| South Korea, Jeollanam-do, Yeongam-gun, Geumjeong-myeon | 251 | | | Solar Integration | Rural | 27 December 2022 | 1.8 | Operational | E2News.com |
| South Korea, Jeollanam-do, Damyang-gun, Mujeong-myeon, Deokgok-ri | 9.1 | 2.5 | Samsung SDI | Solar Integration | Rural | 8 December 2022 | 5.5 | Operational | E2News.com |
| China, Hainan | 50 | 25 | Ruipu | Solar Integration | | 20 October 2022 | 0 | Commissioning | china5e.com |
| South Korea, Pangyo | | | SK On | | Datacenter | 15 October 2022 | | | DCD |
| US, CA, Moss Landing | 730 | 182.5 | Tesla | Energy Shifting, Ancillary Services | Substation | 20 September 2022 | 0.5 | Operational | KSBW News |
| South Korea, Incheon | 103 | 103 | Samsung SDI | Energy Shifting | Factory | 6 September 2022 | | Operational | Teller Report |
| US, Wyoming, Yellowstone National Park | | | | Solar Integration | | 6 September 2022 | | | National Park Service |
| US, CA, Rio Dell | | | Lead Acid | Solar Integration / Backup | Rural | 3 August 2022 | 4 | Operational | KRCR |
| France, Corsica, Poggio-di-Nazza | 4 | 4 | LG Chem | Solar integration | Solar + storage | 3 June 2022 | 1.8 | Operational | BEA-RI investigation report |
| South Korea, Jangseong-gun | | | | Solar Integration | | 2 May 2022 | | | Newspim |
| South Korea, Eoryang‑ri, Mangseong‑myeon, Iksan‑si, Jeollabuk‑do | | | Samsung SDI | Solar+Storage | | 1 May 2022 | | | Post Journal |
| South Korea, Eoryang-ri, Mangseong-myeon, Iksan-si, Jeollabuk-do | | | Samsung SDI | Solar+Storage | | 1 May 2022 | | | Post Journal |
| US, AZ, Chandler | 40 | 10 | LG Chem [NMC] | | Substation | 18 April 2022 | 3 | Operational | AZ Central |
| US, CA, Valley Center | 560 | 140 | LG Energy Solution | | Rural | 5 April 2022 | 0.2 | Operational | Valley Road Runner |
| Taiwan, Taichung City, Longjing District | 1 | 1 | | Solar Integration | Power Plant | 30 March 2022 | 2 | Operational | Yantai Chuangwei Technology |
| US, CA, Moss Landing | 400 | 100 | LG Energy Solution | Solar Integration | Power Plant | 13 February 2022 | 1 | Operational | KSBW News |
| South Korea, Gunwi-gun, Gyeongsangbuk-do | 1.5 | 0.45 | LG Energy Solution | Solar integration | Rural | 17 January 2022 | 3 | Operation. Fully charged | E2News |
| South Korea, Nam-gu, Ulsan | 50 | 10 | SK Innovation | Peak Load Reduction | Urban | 12 January 2022 | 2 | Operational | E2News |
| China, 2022 Incident A | | | | | | 1 January 2022 | | | Confidential |
| China, 2022 Incident B | | | | | | 1 January 2022 | | | Confidential |
| China, 2022 Incident C | | | | | | 1 January 2022 | | | Confidential |
| China, 2022 Incident D | | | | | | 1 January 2022 | | | Confidential |
| US, 2022 Incident A | | | | | | 1 January 2022 | | | Confidential |
| US, 2022 Incident B | | | | | | 1 January 2022 | | | Confidential |
| US, CA, Moss Landing | 1,200 | 300 | LG Energy Solution | Solar Integration | Power Plant | 4 September 2021 | 0.8 | | Vistra |
| Australia, Victoria, Moorabool | 450 | 300 | Tesla [NMC] | Grid Stability | Rural | 30 July 2021 | 0 | Construction, Commissioning | Investigation Report |
| US, IL, LaSalle | 36 | 36 | Sinexcel [LFP] | Solar and Wind Integration, Frequency Regulation | Rural | 19 July 2021 | 1.6 | | WSPY |
| Germany, Neuhardenberg | 5 | 5 | [LFP] | Solar Integration and Frequency Regulation | Indoor/Hangar | 18 July 2021 | 5 | | RBB 24 (Translated) |
| France, New Caledonia, Boulouparis | 10 | 16 | | Solar Integration | Rural | 13 July 2021 | 1.7 | | La 1ere (Translated) |
| US, MI, Standish | 32 | | | Demand Charge Mgmt | Substation | 19 April 2021 | | | WSGW |
| China, Beijing | 25 | | Gotion High-Tech [LFP] | Solar Integration | Commercial | 16 April 2021 | 2 | Construction, Commissioning | Investigation Report (English Translation) |
| Australia, Bohle Plains | 8 | 4 | Tesla | VPP | | 7 April 2021 | 1.2 | Commissioning | Queensland Government |
| South Korea, Hongseong | | | LG Energy Solution | Solar Integration | | 6 April 2021 | 3 | | Business Korea |
| South Korea, Gyeongbuk, Yeongcheon | | | LG Energy Solution | Solar Integration | | 11 March 2021 | | | Social construction of fire accidents in battery energy storage systems in Korea |
| France, Ariege, Perles-et-Castelet | 0.5 | 0.5 | Narada | Hybrid Supercacitor plus Storage System | Substation | 1 December 2020 | 0 | Commissioning, testing | Investigation Report (English Translation) |
| UK, Liverpool | 10 | 20 | | Frequency Regulation | | 15 September 2020 | 1.5 | | Investigation Report |
| South Korea, North Chungcheong, Eumseong | | | LG Energy Solutions | | | 3 September 2020 | | | Korea Economy |
| South Korea, Haenam | | | Samsung SDI | Solar Integration | Field | 27 May 2020 | 2.2 | | E2 News (Translated) |
| Australia, Brisbane | | | | | | 17 March 2020 | | | Brisbane Times |
| China, 2020 Incident A | | | | | | 1 January 2020 | | | Confidential |
| South Korea, Gimhae | 2.2 | | Samsung SDI | Solar Integration | | 27 October 2019 | 1.5 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
| South Korea, Hadong | 1.3 | | LG Chem | Solar Integration | Mountains | 21 October 2019 | 1.2 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
| South Korea, Gunwi | 1.5 | | LG Chem | Solar Integration | Mountains | 29 September 2019 | 1.8 | Discharging | Social construction of fire accidents in battery energy storage systems in Korea |
| South Korea, Pyeongchang | 21 | | Samsung SDI | Wind Integration | Mountains | 24 September 2019 | 2.7 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
| France, Vitry-sur-Seine | | | | | Datacenter | 16 September 2019 | | Maintenance | Univers Freebox |
| South Korea, Yesan | 1.5 | | LG Chem | Solar Integration | Mountains | 30 August 2019 | 1.7 | Charged, inactive | Social construction of fire accidents in battery energy storage systems in Korea |
| US, CA, Camp Pendleton | | | | | | 2 June 2019 | | | CA Spill Database |
| South Korea, North Jeolla, Jangsu | 1 | | | Solar Integration | Mountains | 26 May 2019 | 1 | Charged, discharging | Seoul Finance |
| South Korea, North Gyeongsang, Chilgok | 3.7 | | LG Chem | Solar Integration | Mountains | 4 May 2019 | 2.2 | Charged, inactive | Munhwa Ilbo |
| US, AZ, Surprise | 2 | 2 | LG Chem [NMC] | Volt Reg., PQ, Solar int. | Substation | 19 April 2019 | 2.1 | | APS Investigation Report |
| US, OR, Tualatin | | | Powin Energy | Manufacturing/Testing | | 11 April 2019 | 0 | Testing | Oregon Live |
| South Korea, Ulsan | 46.8 | | | Demand Charge Mgmt | Factory | 21 January 2019 | 0.6 | Charged, inactive | MOTIE Investigation, June 2019 |
| South Korea, North Jeolla, Jangsu | 2.5 | | | Solar Integration | Mountains | 15 January 2019 | 0.8 | Charged, inactive | MOTIE Investigation, June 2019 |
| South Korea, South Gyeongsangnam, Yangsan | 3.3 | | LG Chem | Demand Charge Mgmt | Factory | 14 January 2019 | 0.8 | Charged, inactive | Steal & Metal News |
| South Korea, South Jeolla, Wando | 5.2 | | INCELL | Solar Integration | Mountains | 14 January 2019 | 1.2 | Charging | TvChosun |
| China, 2019 Incident A | | | | | | 1 January 2019 | | | Confidential |
| South Korea, Gangwon, Samcheok | 2.7 | | | Solar Integration | Mountains | 22 December 2018 | 1 | Charged, inactive | Korea Economics |
| South Korea, North Chungcheong, Jecheon | 9.3 | | LG Chem | Demand Charge Mgmt | Mountains | 17 December 2018 | 1 | Charged, inactive | Yonhap News Agency |
| South Korea, South Gyeongsang, Geochang | 1.3 | | LG Chem | Solar Integration | Mountains | 22 November 2018 | 0.6 | Charged, inactive | Gyeongnam Newspaper |
| South Korea, Gyeongsangbuk-do, Mungyeong | 4.2 | | LG Chem | Solar Integration | Mountains | 21 November 2018 | 0.9 | Charged, inactive | JTBC News |
| South Korea, North Gyeongsang, Yeongju | 3.7 | | LG Chem | Solar Integration | Mountains | 12 November 2018 | 0.8 | Charged, inactive | Kyongbuk Ilbo |
| South Korea, South Chungcheong, Cheonan | 1.2 | | LG Chem | Solar Integration | Mountains | 12 November 2018 | 0.9 | Charged, inactive | FPN |
| South Korea, Gyeonggi, Yongin | 17.7 | | Samsung SDI | Frequency Regulation | Factory | 18 October 2018 | 3.2 | Maintenance | E2news |
| South Korea, Jeju | 0.2 | | Revo Co., Ltd. (KEPCO) product use | Solar Integration | | 14 September 2018 | | Charging | Jejusori |
| South Korea, Chungcheongnam, Taean | 6 | | Samsung SDI | Solar Integration | Waterfront | 7 September 2018 | 0 | Installation | Chosun Ilbo |
| South Korea, Chungcheongbuk-do, Yeongdong | 6 | | LG Chem | Solar Integration | Mountains | 1 September 2018 | 0.7 | Charged, inactive | Korea Economics |
| South Korea, Sejong | 18 | | Samsung SDI | Demand Charge Mgmt | Factory | 28 July 2018 | 0 | Installation | Joongdo Ilbo |
| South Korea, South Gyeongsang, Geochang | 9.7 | | Samsung SDI | Wind Integration | Mountains | 21 July 2018 | 1.6 | Charged, inactive | Gyeongnam Newspaper |
| South Korea, South Jeolla, Haenam | 3 | | LG Chem | Solar Integration | Waterfront | 12 July 2018 | 0.6 | Charged, inactive | Kyunghyang Shinmun |
| South Korea, North Jeolla, Gunsan | 19 | | Samsung SDI | Solar Integration | Waterfront | 15 June 2018 | 0.5 | Charged, inactive | No Cut News |
| South Korea, South Jeolla, Yeongam | 14 | | Samsung SDI | Wind Integration | Mountains | 2 June 2018 | 2.4 | Maintenance | Yonhap News Agency |
| South Korea, North Gyeongsang, Gyeongsan | 8.6 | | | Frequency Regulation | Mountains | 2 May 2018 | 1.8 | Maintenance | Yonhap News Agency |
| China, 2018 Incident A | | | | | | 1 January 2018 | | | Confidential |
| China, Shanxi | | | | | | 21 December 2017 | | | Sohu |
| Belgium, Drogenbos | | 6 | | Frequency Regulation | Research Park | 11 November 2017 | | | GTM |
| South Korea, North Jeolla, Gochang | 1.5 | | | Wind Integration | Waterfront | 2 August 2017 | 0 | Installation | MOTIE Investigation, June 2019 |
| China, Shanxi | | | | | | 7 March 2017 | | | Sohu |
| US, WI, Franklin | | | | | Factory | 10 August 2016 | 0 | Assembly, Installation | S&C |
| US, WA, Port Angeles | | | | Energy Shifting | Mall | 3 July 2013 | | | Peninsula Daily News |
| US, AZ, Flagstaff | 1.5 | 0.5 | | Solar integration | | 26 November 2012 | 1.5 | | AZ Daily Sun |
| US, HI, Kahuku | 10 | 15 | Xtreme [PbA] | Wind Integration | Island | 1 August 2012 | 1.5 | | Hawaii News Now |
| Japan, Ibaraki Prefecture | | 2 | NGK [NaS] | | Industrial | 21 September 2011 | | | NGK |
Figure 1. A breakdown of the stationary energy storage failure events from the above table.
Other Energy Storage Failure Incidents
This table tracks other energy storage failure incidents for scenarios that do not fit the criteria of the table above. This could include energy storage failures in settings like electric transportation, recycling, manufacturing, etc.
- Note: Missing values in this table reflect unknowns.
| Location | Setting | Capacity (MWh) | Capacity (MW) | Operator / Integrator | Event Date | System Age (yr) | State During Accident | Description | Source |
|---|
| Ireland, Claregalway | Battery manufacturer | | | Xerotech | 29 January 2025 | | Stored in container | Fire started in a shipping container used to store battery modules at Xerotech battery facility. Damaged batteries were isolated to prevent spread to other parts of facility. Crews have been using water to moderate overheating. Water is being recirculated to prevent runoff contamination. | Connacht Tribune |
| US, MO, Fredericktown | Battery recycling plant | | | Critical Mineral Recovery | 30 October 2024 | | | A fire and explosion occured at a lithium ion battery recycling plant. Residents north and west of Fredericktown were told to evacuate if they could smell smoke. The evacuation order was revised within a couple hours to cover only residents (approx. 25 homes) living on the same road as the recycling plant. Other residents were asked to shelter in-place. The fire was controlled after 3 days and hot spots requiring fire suppression remained 8 days later. The EPA conducted air monitoring and found that concentrations of contaminants remained below thresholds. 2 days after the fire broke out, a 3 mile fish kill was discovered in Little St. Francis River. Firefighting foam is hypothesized to be the cause. Drinking water was not affected. | Missouri Independent |
| US, CA, San Pedro | On road during transport | | | | 26 September 2024 | | In transit | A truck hauling 60,000 lbs of lithium ion batteries overturned and resulted in a deflagration and a fire. The freeway and bridge were shut down along with 6 port terminals. Firefighters utilized a defensive firefighting strategy to monitor and contain the fire. After 24 hours, the smoldering container was moved off the road to an open lot for monitoring, and the roads were re-opened after hazardous materials were cleared. | LB Post |
| Canada, Montreal | Temporary storage at a port | | | | 23 September 2024 | | | A container storing 15,000 lbs of lithium ion batteries on land caught fire at the Port of Montreal. Firefighters sprayed the container with water to cool it without opening the container. The City of Montreal ordered a lockdown for nearby residents due to concerns about the smoke. | CTV News |
| US, NV, Nye County | On highway during transport | | | | 17 September 2024 | | In tranit | A semi-truck hauling lithium ion batteries sideswiped another semi-truck headed in the opposite direction, shortly after midnight on I-95. The resulting fire was extinguished and the road cleared by a HAZMAT crew. The road was reopened approximately 18h after the crash was reported. | Review Journal |
| Germany, Thuringia | Temporary storage | | | Suncycle | 11 August 2024 | | Temporarily stored onsite; not interconnected | A group of batteries that was intended for disposal and was being temporarily stored at the site caught fire. An employee used a forklift to move the burning storage unit to prevent propagation, and was suffered minor injuries due to the fumes and smoke. This incident is the third in a series of incidents at the Suncycle site. | PV Magazine |
| US, South Carolina, Seneca | Manufacturing | | | BorgWarner | 8 August 2024 | | Battery on assembly line | A lithium ion battery caught fire on the assembly line at a manufacturing facility. The fire department got the fire under control after 2.5 hours. | WSPA |
| US, CA, Baker | On highway during transport | | | | 26 July 2024 | | In transit | A truck hauling lithium ion batteries was involved in a crash, overturning the truck and resulting in a fire. The I-15 freeway, a major artery between South California and Las Vegas, was shut down for two days. Several drivers stuck in the resulting traffic and high temperatures of the day experienced heat-related medical issues. | CBS |
| Germany, Thuringia | | | | Suncycle | 30 June 2024 | | | This incident is the second in a series of incidents at the Suncycle site. The fire department used a controlled burn approach to avoid costly disposal of contaminated firewater. The fire was extinguished after 12 hours. Nearby residents were advised to keep windows closed due to smoke. | MDR.DE |
| South Korea, Hwaseong | Manufacturing | | | Aricell | 24 June 2024 | | | A single battery cell in the factory caught fire and spread to the 35,000 battery cells stored on the factory's second floor, producing a series of explosions. 22 workers were killed and 8 were injured in the fire. | New York Times |
| Germany, Thuringia | | | | Suncycle | 7 June 2024 | | | A battery caught fire at an engineering and test center. Firefighters used a grappling hook to open the container’s doors, cool the batteries with water, and extinguished the fire after 4 hours. The affected container was pulled away from the other battery containers with a tractor to prevent the flames from spreading. The contaminated firewater was disposed of. This incident is the first of a series of incidents at the Suncycle site. | PV Magazine |
| Germany, Neermoor | Temporary storage | | | Intilion | 27 April 2024 | | Temporarily stored onsite; not interconnected | One of several lithium-ion containers located in an industrial area was observed to be smoking. The containers were not interconnected to the grid. The fire department consulted with the operator and opened the container, resulting in an explosion. Two firefighters were injured. The container was cooled and moved away from the surrounding containers with a crane to prevent propagation. The fire was extinguished in 10 hours. A highway was closed overnight for 6 hours and residents were asked to keep doors and windows closed due to the heavy smoke. | Neermoor Fire Brigade |
| US, Ohio, Columbus | | | | | 18 April 2024 | | | A tractor trailer with 5900 lbs of lithium ion batteries caught fire. A bomb squad used a robot to cut a hole in the trailer during firefighting to reduce the risk of explosion. The evacuation order was lifted after three hours. | Firehouse |
| Scotland, Kilwinning | Recycling | | | | 8 April 2024 | | | A fire broke out at the Fenix battery recycling plant. The cause of fire is under investigation. | BBC |
| Australia, Maryborough | On highway during transport | | | | 22 March 2024 | | In transit | A semi-trailer truck carrying lithium ion batteries was involved in a multi-vehicle highway crash, resulting in a fire. The level of contribution from the batteries to the fire is unknown. | ABC News |
| France, Viviez | Recycling | | | SNAM | 17 February 2024 | | Storage | A fire broke out in a warehouse owned by battery recycling group SNAM. The warehouse stored 900 metric tons of lithium ion batteries. The cause of the fire is unknown. | Reuters |
| US, AK, Dutch Harbor | Maritime | | | | 29 December 2023 | | In transit | The ship was transporting lithium-ion batteries from Vietnam to San Diego. The fire began in a hold, which was pumped with carbon dioxide and sealed. The cause of the fire is unknown. | AP News |
| Germany, Wurzburg | Underground Parking Garage | | | | 5 November 2023 | | | A metal lattice box filled with batteries released smoke into the underground parking garage. Fire fighters extinguished the fire in three hours and used a high pressure fan to clear the smoke. | Fireworld |
| Netherlands, Ameland | Maritime | | | Multiple | 26 July 2023 | | Storage | A cargo ship fire burned for over a week. The crew was evacuated, after 1 death, and the ship was monitored for potential capsizing that could have damaged the nearby UNESCO World Heritage - listed wildlife habitat. The ship was carrying over 3700 new vehicles, with ~500 reported to be EVs. The cause of the fire is unknown. | AP |
| France, Rouen | Warehouse | | | | 16 January 2023 | | Storage | A fire spread through a warehouse containing thousands of lithium ion batteries. | the deep dive |
| US, CA, Baker | Electric Vehicle Charging Station | | | Tesla | 1 January 2023 | | Operational | This Megapack on a trailersystem is used to boost charging infrastructure at busy supercharger stations during peak times. | Electrek |
| Germany, Kaufbeuren | Battery test laboratory | | | | 3 November 2022 | | Testing | A battery exploded while undertest at an Intertek battery testing facility. | Allgau Newspaper |
| US, CA, Palo Alto | EV Dealership | | | Tesla | 7 August 2022 | | Storage | Failure within a stack of uninstalled EV batteries led to thermal runaway and damage to all batteries and some nearby property. | Palo Alto Fire Dept. |
| Netherlands, Amsterdam | Maritime | 0.7 | | EST-Floattech | 25 July 2022 | 1 | In transit / operation | Battery fire on Diesel-Electric hybrid river boat | The Maritime Executive |
| US, WI, Milwaukee | Hospital parking garage | | | | 21 June 2022 | | recycling bin | Container holding recycled batteries exploded in parking garage | WISN |
| Sweden, Karlskoga | Warehouse | | | | 10 April 2022 | | | A fire outside of a warehouse where a large number of batteries were being stored. | SVT Nyheter |
| South Korea, North Chungcheong, Cheongju | Manufacturing | | | EcoPro BM | 21 January 2022 | | Operational Manufacturing Facility | | Korea JoongAng Daily |
| China, Wuhan | On highway during transport | | | | 12 January 2022 | | during transportation | | Jimu News |
| US, IL, Morris | Warehouse | | | Superior Battery Inc. | 2 July 2021 | | | | ABC |
| US, NM, Albuquerque | Recycling | | | Friedman Recycling | 16 March 2021 | | | | KOB |
| Norway, Oslo Fjord | Maritime | 0.8 | | Corvus Energy | 11 March 2021 | 2 | | | Corvus Energy |
| China, Yunnan, Qujing | Manufacturing | | | CATL | 27 January 2021 | | | | ESP |
| China, Hunan | Recycling | | | CATL, Brunp Recycling | 7 January 2021 | | | | ESP |
| Norway, Sydnes | Maritime | 2 | | Corvus Energy | 10 October 2019 | 0.5 | | | CFPA Europe |
| US, OR, Powin | New product testing | | | Powin HQ | 11 April 2019 | | | | The Oregonian |
- ↑ This database was formerly known as the BESS Failure Event Database. It has been renamed to the BESS Failure Incident Database to align with language used by the emergency response community. An ‘incident’ according to the Federal Emergency Management Agency (FEMA) is an occurrence, natural or man-made, that requires an emergency response to protect life or property, while an ‘event’ is a planned, non-emergency activity. The use of incident is prevalent, for example, in referring to the Incident Command, or Incident Command System used by public and private agencies to coordinate incident management operations. See